77
V ESW Brasil 2011 Seminário Internacional de Engenharia Elétrica na Segurança do Trabalho São Paulo 8 a 10 de novembro Holiday Inn Parque Anhembi Innovative Techniques for Mitigating Arc Flash Exposure David Shipp Eaton Corporation Electrical Sector

AF Solutions

Embed Size (px)

DESCRIPTION

Incident Energy

Citation preview

  • V ESW Brasil 2011 Seminrio Internacional de Engenharia

    Eltrica na Segurana do Trabalho

    So Paulo 8 a 10 de novembro Holiday Inn Parque Anhembi

    Innovative Techniques for

    Mitigating Arc Flash Exposure

    David Shipp

    Eaton Corporation Electrical Sector

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    ABSTRACT

    As more and more industry addresses arc flash electrical

    safety concerns, they are discovering high risk associated with

    what used to be normal maintenance tasks. In many cases,

    the excessively high arc flash incident energies make it so all

    maintenance must be done with equipment de-energized not always acceptable to the process industries. This paper will

    address the multiple ways the authors have devised to

    significantly lower arc flash incident energy exposure by new

    system design and products, retrofits, retro-fills, equipment

    modifications, alternate protection settings, etc. In most

    cases, NFPA 70E Hazard Risk Category 2 or lower can be

    obtained. Several real world examples will be discussed.

    .

    2

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    DEVELOPMENTS LEADING TO NFPA 70E

    Large Hydro in Pacific NW

    6.9kV Switchgear

    Racking in Breaker

    AF occurred

    One worker injured

    4+ years, $10+ million

    3

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    NFPA 70E METHODS FOR SELECTING

    PROTECTIVE CLOTHING AND PPE

    NFPA 70E-2004 Table 130.7(C)(11) Protective Clothing Characteristics

    Hazard Risk

    Category

    Clothing Description (Typical number of clothing layers is given in parenthesis)

    Required Minimum Arc Rating of PPE [J/cm2(cal/cm2]

    0

    Non-melting, flammable materials (i.e., untreated cotton, wool, rayon, or silk, or blends of these materials) with a fabric weight at least

    4.5 oz/yd2 (1)

    N/A

    1 FR shirt and FR pants or FR coverall (1) 16.74 (4)

    2 Cotton underwear conventional short sleeve and brief/shorts, plus FR shirt and FR pants (1

    or 2) 33.47 (8)

    3 Cotton underwear plus FR shirt and FR pants

    plus FR coverall, or cotton underwear plus two FR coveralls (2 or 3)

    104.6 (25)

    4 Cotton underwear plus FR shirt and FR pants

    plus multilayer flash suit (3 or more) 167.36 (40)

    4

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 5

    INTRODUCTION

    Too Much PPE is Just

    as Bad as Not Enough!

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    PROTECTIVE CLOTHING AND PPE FOR

    ARC FLASH

    Multi-Layering Testing

    6

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Specialized Arc Flash Protective Equipment

    Flash Suits / Switching Coats

    Two-Layer Flash Suit,

    ATPV = 42 cal/cm2

    Use: Hazard/Risk Category 4

    PROTECTIVE CLOTHING AND PPE FOR

    ARC FLASH

    7

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    REDUCING ARC FLASH HAZARDS

    Need a Total System

    Solution Approach

    8

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    SOLUTIONS THAT REDUCE ARC

    FLASH INJURIES AND DAMAGE

    Label Equipment & Train Personnel

    Minimize Risk with Good Safety Practices

    Reduce Available Fault Current

    Faster Clearing Time

    Move People Further Away

    Redirect Blast Energy

    Prevent Fault

    9

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 10

    ARC FLASH SOLUTIONS

    Bypass Isolation A.T.S. Arc Flash Reduction Maintenance

    System for new and old (Retrofit

    Kits) installations (LV and MV)

    Arc Resistant MV Motor Starters MV and LV Arc Resistant Switchgear Bus Differential Schemes MV and LV Zone Selective

    Interlocking

    Current Limiting Reactors LV/MV Remote Racking Hi (or Low) Impedance Transformers MV / LV HRG Systems AF Power System Studies Insulated Bus in Switchgear

    Infra-Red Windows Kirk Key Interlock Systems MCC Bucket & Safety Switch Viewing

    Windows MCC Bucket Retrofits Partial Discharge Systems Infra-Red Sensors in Hi AF Areas

    (Dont Have to Remove Covers) AF Tested Current-Limiting MCCBs Remote Monitoring, Control and

    Diagnostics LV/MV Remote Operators Arc Mitigator Light Detection

    Tripping (MV and LV) AFL System (No Main 2ndary

    Breaker)

    Examples of Arc-Flash Solutions:

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    REDUCING ARC FLASH HAZARDS

    Label Equipment

    Train People

    Wear PPE

    11

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Engineering Studies Arc Flash Analysis

    Arc Flash Studies Standardized Data Collection

    Templates

    Power Systems Engineers

    Labels, Training,

    Recommendations

    12

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Provides guidance for the calculation of incident energy and arc flash protection

    boundaries.

    It presents formulas for numerically quantifying these values.

    The IEEE 1584 Guide also includes an Excel Spreadsheet Arc-Flash Hazard Calculator which performs the actual calculations using the formulas stated

    in the Guide.

    13

    IEEE 1584-2002: Guide for Performing Arc Flash Hazard Calculations

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Personal Protective Equipment (PPE)

    Cumbersome Hot Reduces Mobility Increases Fatigue

    14

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Arc-Flash Safety for electricians, technicians or equipment operators whose employers have

    already declared them to be "qualified" according

    to OSHA rules but need to be recycled or be

    updated with any new revision of NFPA 70E

    Electrical and Arc-Flash Safety for electricians, technicians and equipment operators who are not

    "qualified" but who might be exposed to arc-flash

    hazards

    Understanding Arc Flash for engineers, safety managers, consultants and electricians

    15

    Recommended Training

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Minimize Risk with Good Safety Practices

    De-Energize Equipment versus Working It Live unless increased hazards exist or infeasible due

    to design or operational limitations.

    Switching remotely (if possible)

    Closing and tightening door latches or door bolts before operating a switch.

    Standing to the side and away as much as possible during switching operations.

    16

    Practical Methods for Reducing

    Arc Flash Hazards

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 17

    Minimize Risk with Good Safety Practices

    Bad Exposed Back of Neck Good All of Body Protected

    Practical Methods for Reducing

    Arc Flash Hazards

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    INTRODUCTION

    18

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 19

    Reduce Available Fault Current

    (Reduce Incident Energy)

    Reducing Arc Flash Hazards

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 20

    Lowering Isc Does not Always Lower Incident

    Energy

    Fuse vs Breaker

    No 1 Single Answer

    Must Do Arc Flash Study

    Reducing Incident Energy

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    HRG Units

    Typically Under 5 Amps

    Pulsing Contactor

    Many Options

    LV or MV

    Does Not Preclude PPE

    Lowers Probability of Accident

    22

    High Resistance Grounding (HRG)

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 23

    Faster Clearing Time

    (Reduce Incident Energy)

    Reducing Arc Flash Hazards

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Neither circuit breaker calculation method accounts for

    their current-limiting effects.

    Neither based on any actual circuit breaker test data.

    SIMPLE method is based upon worst case time of 4 manufacturers time/current curves. VERY conservative!

    ALTERNATE method requires

    manufacturer specific time/current curve

    input.

    Concerns with ALTERNATE method too because circuit

    breaker time/current curves are very conservative in their

    instantaneous region.

    24

    LV Circuit Breakers Issues with IEEE 1584

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 25

    MCCBs Arc Flash Performance Comparison

    Apply Current-Limiting Molded-Case Circuit Breakers

    Min Mid Max

    225 A MCCB with Thermal-Magnetic Trip Unit

    Bolted fault current 3.4 kA 35 kA 100 kA

    Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm2) N/A

    1 1.7 4.7

    Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm2) 59.6 1.1 2.3

    Measured Incident Energy (Cal/cm2) 0.08 0.1 0.11

    1200 A MCCB with Electronic Trip Unit

    Bolted fault current 20 kA 35 kA 100 kA

    Inc. Energy via IEEE 1584 Table E.1 Generic (Cal/cm2) N/A

    1 3.5 9.4

    Inc. Energy via IEEE 1584 & Trip Curve (Cal/cm2) 218 3.5 5.8

    Measured Incident Energy (Cal/cm2) 1.86 1.2 1.64

    Incident Energy at

    Bolted Fault Current

    IEEE 1584 Generic Equation

    IEEE 1584 Using Time Current Curve Input

    Tested Value

    1 N/A = Not Applicable

    because it is outside the

    range of the IEEE 1584

    Generic Equation

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    This is only a first step in making MCCB recommendations for arc flash applications.

    It is much easier for novice users to understand the needed PPE, rather than a

    caloric energy value.

    Its important and necessary to have arc flash application recommendations for MCCBs.

    26

    Comments about MCCB Application Arc Flash Performance

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Zone Selectively Interlocked LV Power Circuit Breakers

    provide significantly lower Arc Flash energy values:

    Testing confirms that a LV Power Circuit Breaker

    (4000A maximum) require Category 2 PPE (8 cal/cm2)

    with proper instantaneous settings

    During maintenance it is recommended to temporarily adjust

    the Instantaneous and Ground Fault (if available) trip

    settings to their lowest value

    Unless a Low Voltage Power Circuit Breaker

    operates in the Instantaneous trip mode, the

    arc flash energy values will require Category

    3 PPE or greater

    27

    LV Power Circuit Breakers

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Bus Differential (87B)MV or HV

    Zone Selective Interlocking a Control approach / Form of 87B MV and LV

    Arc Mitigator Light (Current) Detection Systems for MV and LV Switchgear and

    Controlgear

    Current Limiting Fuses*

    28

    High Speed Clearing

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    SD=

    0.5S

    SD=

    0.3S

    SD=

    0.3S

    SD=

    0.3S

    M1

    F1 F2 F3 X

    35kA fault current

    Without ZSI = 0.5 S:

    43.7 Cal/cm2

    Greater than Cat. 4 PPE

    DANGER!

    With ZSI = 0.08 S:

    7.0 Cal/cm2

    FR Shirt & Pants

    Cat. 2 PPE

    29

    Zone Selective Interlocking (ZSI)

    Explanation:

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    An Off-Shore Oil Platform in the Gulf of Mexico lowered their Incident Energy Exposure from

    85 calories down to 12.7 calories by retrofitting

    their 480 V Switchgear with ZSI.

    30

    Zone Selective Interlocking (ZSI)

    Example:

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Door Mounted Components

    Breaker Mounted Components

    Arc flash Reduction

    Maintenance System

    DIGITRIP

    Harness

    Lockout

    Switch

    Battery

    Indicating

    Light

    31

    Arc Flash Reduction Systems Retrofit of LV PCBs

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    An external over-ride switch and circuitry are

    connected to a breakers trip unit, and is adjustable between 2.5X - 10X.

    When a person wants to perform maintenance,

    they close the switch, which automatically over-

    rides all of the delay functions, and causes the

    breaker to trip without any intentional delay

    whenever a fault is detected. Use its lockout

    features for normal lockout tag-out procedures.

    32

    Arc Flash Reduction Systems Retrofit of LV PCBs

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Upon completion of the maintenance, the lock is

    removed, the switch is manually opened, and all

    previous trip unit settings are again re-activated,

    without need for recalibration.

    33

    Arc Flash Reduction Systems

    for LV PCBs

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Overflow Sump Pump Location

    Recommendation (Acceptable)

    C0-5: XFMR protection Main and FDR: Coordination

    Hazard Risk Category

    = HRC = Danger (>40 Cal.)

    AF Current = 5.6kA

    34

    Example: Existing Equipment

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Overflow Sump Pump Location

    Recommendation (Good)

    C0-5: TXMR protection Main and FDR: Coordination New Equipment (Better)

    Replace C0-5 w/ DT3000 Replace FDR trip w/ DigiTrip RMS 610, LSI trip unit.

    Arc flash Reduction System (Best)

    Replace C0-5 w/ DT3000 Replace FDR trip w/ DigiTrip RMS610, LSI trip unit & Arcflash Reduction

    Maintenance Switch.

    Replace Main with Digitrip 610 LS & Arc flash Reduction Maintenance Sw.

    HRC = 1 (< 4 cal/cm2) AF Current = 5.6kA 35

    Arc Flash Reduction Systems Example

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    High Avail Fault Current

    Digitrip610 & Arc flash Reduction System

    Normal settings HRC=3 (10.7 cal)

    With Arc flash Reduction System: HRC= 1 (2.2 cal)

    36

    Arc Flash Reduction Systems Example for High Available Fault Current

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    2000 A fuses supplying 480V Glass Furnaces

    Incident Energy =61 Cal / HRC=Danger

    Retro-filled fuses with LV Power Circuit Breakers

    35 cal with trip Unit/6 cal with New Breaker + Built-in Arc

    Flash Reduction System

    37

    Arc Flash Reduction Systems Retro fill Example

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 38

    Arc Flash Reduction Systems Example of replacement of old LVPCB

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Has 5 user-selectable levels of protection to choose

    maximum protection, while

    avoiding nuisance tripping

    Blue color LED indicating Maintenance mode

    Can be remotely activated through IR communication

    with PDA

    39

    Arc Flash Reduction Systems Example of Integrated Trip Unit

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Computer Room PDU (Bypass Mode)

    Thermal-Magnetic breaker HRC = 4 Due to Long Time

    Replaced with Electronic Trip Breaker HRC = 1

    40

    Change to Electronic Trip Units

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Multiple Settings Groups

    Similar to LV maintenance

    switch, only for MV applications

    Used to reduce the trip delay of

    medium-voltage relays while

    maintenance is being performed

    on equipment.

    Requires relay with multiple

    settings groups capability

    41

    Practical Methods for Reducing Arc

    Flash Hazards

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Switch

    Indicating Light

    m-Processed

    Relay

    42

    Arc Flash Reduction using m-Processed Relay with Group Settings

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 43

    Network Protectors

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 44

    Network Protectors

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 45

    Network Protectors

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 46

    Network Protectors

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 47

    Network Protectors

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 48

    Network Protectors

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 49

    Network Protectors

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Any Exposure / Racking Feeder Circuit-Breakers Must be Cleared by Primary

    Fuse

    100 Cal Exposure

    50

    Substations without Main Secondaries

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    51

    Substations without Main Secondaries

    Arc Flash reduction by Retrofit

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Primary Fuses Only: 594 calories

    Primary Circuit-breaker Only: 289 calories

    Primary Circuit-breaker + Arc Flash Reduction System:

    7.5 calories

    52

    Substations without Main Secondaries

    Arc Flash reduction by Retrofit

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Retrofill Primary Fuse with Vacuum Circuit-breaker

    Sense at 480V Transformer side Trip Primary

    Use Protective Relay with Group Settings

    Many Variations

    Must Meet ANSI C37.59

    53

    Substations without Main Secondaries

    Arc Flash reduction by Retrofit

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 54

    Substations without Main Secondaries

    Arc Flash reduction by Retrofit

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 55

    Substations without Main Secondaries

    Arc Flash reduction by Retrofit

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Safety by Design: Improved Unit Substation Design

    Line

    LA

    CPT

    Load

    CTs

    Snubber

    Bkr

    Typical LV Unit Substation with Vacuum Breaker in MSB (Medium Voltage Switch over Breaker) Assembly

    25H X 20W X 18 D, 330 lbs

    ANSI C37.20 rated at 25 and

    40kA

    600, 1200 and 2000A ratings

    Integral trip unit with linear trip

    actuator

    2-step stored energy

    mechanism

    56

    Substations without Main Secondaries

    Arc Flash solution for new installation

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    XXPXXX-90PXXX-P1,P2,P3,P4

    4-3/C, #500kcmil

    600V, TC, XHHW-2, W/GND

    XXPXXX-L1,L2,L3

    CABLE TRAY

    100 FEET

    XXPXXX-90PXXX-P1,P2,P3,P4

    4-3/C, #500kcmil

    600V, TC, XHHW-2, W/GND

    XXPXXX-L1,L2,L3

    CABLE TRAY

    100 FEET

    XXPXXX-90PXXX-P1,P2,P3,P4

    4-3/C, #500kcmil

    600V, TC, XHHW-2, W/GND

    XXPXXX-L1,L2,L3

    CABLE TRAY

    100 FEET

    XXPXXX-90PXXX-P1,P2,P3,P4

    4-3/C, #500kcmil

    600V, TC, XHHW-2, W/GND

    XXPXXX-L1,L2,L3

    CABLE TRAY

    100 FEET

    LV Swgr Elevation Substation One-Line

    VCB

    ZSI ZSI ZSI ZSI

    ZSI

    50 51

    50 51

    (3) 600:5 CT

    (3) 3200:5 CT

    (3) 3200:5 CT

    57

    Safety by Design: Improved Unit Substation Design

    Substations without Main Secondaries

    Arc Flash solution for new installation

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 58

    Light Detection System Arc Flash reduction for MV Switchgear

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 59

    Light Detection System Arc Flash reduction for MV Switchgear

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    REDUCING ARC FLASH HAZARDS

    Move People Further Away

    60

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Remain physically outside the flash protection boundary.

    Therefore NO ARC FLASH HAZARD protection required.

    61

    Arc Flash Reduction Remote Racking of MV CB 5/15/27/38 kV Switchgear

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    VS.

    62

    Arc Flash Reduction Remote Racking of MV CB 5/15/27/38 kV Switchgear

    X

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Without With

    63

    Arc Flash Reduction Remote Switching (Chicken Switch)

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Accessory for Remote Operation of Isolation Switch: Increased Operator

    Safety.

    Temporarily mounts to front of Starter door equipped with mounting

    provisions.

    Operation by Control Station connected to Motor Operator via 25-

    foot Cable.

    64

    Arc Flash Reduction Remote Operation of Isolation Switch

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 65

    Arc Flash Reduction Motor Operated Isolation Switch

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    REDUCING ARC FLASH HAZARDS

    Redirect Fault Energy

    66

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Redirects Arc Energy and Particulates

    67

    Arc Resistant Switchgear

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Arc Flaps

    2000A or 3000A

    breaker with Vent

    1200A can be 1

    high or 2 high

    Control

    Section

    VT drawer

    Manual Close/Open Push

    Buttons 68

    5/15 kV Arc Resistant Switchgear

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Test @ 65kA / 508V

    Arc initiated in breaker

    compartment

    Plenum Design

    March 2008 - PASS

    Arc out-gassing through

    plenum

    No arc flash out of the

    front of the gear

    69

    LV Arc Resistant Switchgear Testing

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    REDUCING ARC FLASH HAZARDS

    Prevent Fault

    70

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section 71

    LV MCC Racking buckets with front door closed

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Bucket Position

    Connected

    Test

    Withdrawn

    Handle Mechanism

    Device Island

    Start, Stop, Auto, Man

    Unit Latch

    Breaker

    Internal Shutter Position

    Open

    Closed

    Racking Tool Receiver

    Starter

    72

    LV MCC Withdrawable units with increased safety features

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Racking Tool

    Receiver: 3/8 Square

    Internal Shutter

    Position:

    Open/Closed

    Bucket Position:

    Connected/Test/Disconnected

    Stab Positive

    Position Indicator:

    With lockout tag out

    hole

    Breaker Operator

    Test Position Block:

    Phase Voltage,

    Control, voltage,

    Ground 73

    LV MCC Withdrawable units with increased safety features

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    DC Motor Wireless Option

    Attaches Easily

    Minimal Torque Required

    25 Foot Pendant Station

    It should interfaces with other

    Remote Racking Systems

    74

    LV MCC Racking buckets with front door closed

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Infrared Scanning Windows for LV/MV Assemblies

    79

    Safety Related Solutions

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    Monitoring connecting joints on a PDU, utilizing

    Plastic Bracket System

    Monitoring Individual Connections

    80

    Continuous Thermal Monitoring

  • 2011 IEEE The Institute of Electrical and Electronics Engineers, Inc. - Industry Applications Society - South Brazil Section

    QUESTIONS?

    82

  • V ESW Brasil 2011 Seminrio Internacional de Engenharia

    Eltrica na Segurana do Trabalho

    So Paulo 8 a 10 de novembro Holiday Inn Parque Anhembi

    Thank you!

    David Shipp

    Eaton Corporation Electrical Sector