PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
2#2,5mm²
20A
A
32A
4#6,0mm²
CA#6,0mm²
VE
NT
ILA
DO
RE
S
DIR
EIT
A
2#2,5mm²
20A
CA
IX
AS
D
E
SO
M
DIR
EIT
A
2#2,5mm²
20A
2#2,5mm²
20A
RE
SE
RV
A
RE
SE
RV
A
VEM DO QDCTE.02
B B
ECTE03-01
VD-02
ECTE03-03
ECTE03-03
ECTE03-03
ECTE03-04
ECTE03-04
ECTE03-04
ECTE03-05
ECTE03-05
ECTE03-06
ECTE03-06
ECTE03-07
ECTE03-08
ECTE03-10
ECTE03-01
VD-03
ECTE03-01
VCABINE
ECTE03-02
VE-01
ECTE03-02
VE-02
ECTE03-02
VE-03
VD-02
VE-02
VD-01
VE-01
VD-03
VE-03
ECTE03-01
VD-01
EC
TE
03-01
EC
TE
03-03
2#2,5mm²
20A
C
VE
NT
ILA
DO
RE
S
ES
QU
ER
DA
EC
TE
03-02
CA
IX
AS
D
E
SO
M
ES
QU
ER
DA
EC
TE
03-04
B
TO
M. U
SO
GE
RA
L
EC
TE
03-05
2#2,5mm²
20A
C
TO
M. U
SO
GE
RA
L
EC
TE
03-06
2#2,5mm²
20A
A
TO
M.
EQ
.
SO
M
EC
TE
03-07
2#2,5mm²
20A
C
TO
M.
EQ
.
SO
M
EC
TE
03-08
2#2,5mm²
20A
B
ILUMINAÇÃO
CA
BIN
E
EC
TE
03-09
RE
SE
RV
A
I1a
I1a
10- ELETRODUTOS NÃO COTADOS DEVERÃO SER DE Ø3/4".
FASE C ... BRANCA
NEUTRO ... AZUL
FASE A ... PRETO
RETORNO... CINZA
FASE B... VERMELHA
TERRA ... VERDE/AMARELA
2-CONDUTORES NÃO ESPECIFICADOS SERÃO EM COBRE, FLEXÍVEL, COM DUPLA CAMADA
DE ISOLAMENTO EM PVC, 750V, SEÇÃO MÍNIMA #2,5mm². TODOS OS CABOS DEVERÃO SER
DO TIPO NÃO PROPAGANTE À CHAMA, COM AUTO-EXTINÇÃO DO FOGO, CONSTATADO
ATRAVÉS DE ENSAIOS, POSSUÍREM PROPRIEDADES EXCLUSIVAS DE BAIXA EMISSÃO DE
FUMAÇA E GASES TÓXICOS. REF.: AFUMEX PRYSMIAN;
11-SONDAR TODOS OS ELETRODUTOS PREVIAMENTE, COM ARAME GALVANIZADO N°14 BWG
PARA PERMITIR A CORRETA PASSAGEM DOS CABOS;
12-AS EMENDAS, QUANDO NECESSÁRIAS, DEVERÃO SER SEMPRE FEITAS NO INTERIOR DAS
CAIXAS DE PASSAGEM, DEVENDO SER ISOLADAS COM FITA DE AUTO FUSÃO E FITA
CONVENCIONAL;
14-DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE ACABAMENTO EM TODAS AS
EXTREMIDADES DE ELETRODUTOS, EXCETO NOS QUE TERMINAM EM CAIXAS DE SAÍDA.
6-ISOLAR O CONECTOR DE DERIVAÇÃO COM FITA AUTO-FUSÃO E CONVENCIONAL. O CABO
PRINCIPAL NÃO DEVERÁ SER SECCIONADO NO PONTO DE DERIVAÇÃO;
16-OS DISJUNTORES DEVERÃO SER IDENTIFICADOS ATRAVÉS DE PLACAS ACRÍLICAS E A
FIXAÇÃO DESTES DISJUNTORES SERÁ POR ENGATE RÁPIDO EM TRILHO DIN;
5-NA DISTRIBUIÇÃO DE QUALQUER CIRCUITO, OS CABOS NEUTRO E TERRA DEVERÃO SER
EXCLUSIVOS, NÃO SENDO ACEITOS TERRA OU NEUTRO COMUNS A OUTROS CIRCUITOS;
3 - TODOS OS CABOS DEVERÃO SER ANILHADOS (IDENTIFICAÇÃO DOS CABOS) EM TODAS
AS CAIXAS, CAIXAS DE PASSAGEM E/OU CONDULETES.
1 - COTAS EM MILÍMETROS, EXCETO ONDE INDICADO. CONSIDERAR AS COTAS
PRIORITÁRIAS EM RELAÇÃO À ESCALA.
9- TODOS OS ELETRODUTOS OU TRECHOS DE ELETRODUTOS APARENTES OU NO INTERIOR
DE ESPAÇOS DE CONSTRUÇÃO ( ENTREFORRO, SHAFT) DEVERÃO UTILIZAR ELETRODUTOS
DO TIPO LEVE DE AÇO GALVANIZADO ELETROLITICAMENTE, CONFORME NBR 13.057.
13- OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE
DUAS CURVAS, EVITANDO-SE TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL.
7- TODAS AS CONEXÕES DE CONDUTORES ENTRE SI E COM OUTROS COMPONENTES DA
INSTALAÇÃO, DEVEM GARANTIR CONTINUIDADE ELÉTRICA DURÁVEL E ADEQUADA
SUPORTABILIDADE E PROTEÇÃO MECÂNICA. DEVERÃO ADEQUADAS SER APLICADAS COM
FERRAMENTAS
8- ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO ATRAVÉS
DO CABO DE PROTEÇÃO Pe (TERRA) MAIS PRÓXIMO.
17- TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60 947-2
COM CURVAS DE ATUAÇÃO TIPO "B", "C", OU "D", CONFORME INDICAÇÃO.
18- O QUADRO SERÁ DE MATERIAL ISOLANTE , DE EMBUTIR (CONFORME PROJETO) , COM
NO MÍNIMO IP-30, PROVIDO DE ALETAS PARA VENTILAÇÃO E PORTA COM CHAVE E
TRINCO, DEVENDO POSSUIR, SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO NBR IEC
60439, EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS.
19 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS
ATRAVÉS DE ETIQUETAS ACRÍLICAS, CONFORME NOMES DOS CIRCUITOS CONSTANTES
NO QUADRO DE CARGAS CORRESPONDENTE.
20 - ATERRAR TODAS AS PARTES METÁLICAS DOS QUADROS ATRAVÉS DE CABO DE COBRE
ISOLAÇÃO VERDE, EM PVC 70°C 750V.
21- O QUADRO DEVERÁ POSSUIR IDENTIFICAÇÃO DO QUADRO, TENSÃO E FREQUÊNCIA NA
FACE EXTERNA DE SUA PORTA, EM ETIQUETA INDELÉVEL DE FUNDO PRETO E LETRAS
BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO QUADRO.
22- O QUADRO DEVERÁ POSSUIR ETIQUETA ACRÍLICA DE IDENTIFICAÇÃO DOS CIRCUITOS E
FECHADURA E TER SEU DIAGRAMA AFIXADO EM SUA PORTA (INTERNAMENTE),
23- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE
COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE
FUMAÇA 70 ºC 750V.
24 - TODOS OS CABOS NO INTERIOR DO QUADRO DEVERÃO RECEBER ETIQUETAS DE
IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO A QUE ESTÁ LIGADO
25 - EM TODOS OS QUADROS (QDC'S) APRESENTADOS NESSE PROJETO, FORAM
PREVISTOS ESPAÇOS RESERVAS MÍNIMOS CONFORME NBR 5410 PARA AMPLIAÇÕES
FUTURAS, COM BASE NO NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADOS.
26 - DEVERÃO SER PREVISTAS CANALETAS DISTRIBUÍDAS NO INTERIOR DO QUADRO
ELÉTRICO PARA A PASSAGEM DOS CABOS DOS CIRCUITOS TERMINAIS. É IMPORTANTE
SALIENTAR QUE DEVERÁ SER RESPEITADA A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS
NESSAS CANALETAS, SEGUNDO ORIENTAÇOES DA NBR 5410/2004.
4 - OS CONDUTORES DEVERÃO SER IDENTIFICADOS PELA COR DE SEU ISOLAMENTO
CONFORME SEGUE:
15- TODAS AS TOMADAS DEVERÃO SER IDENTIFICADAS ATRAVÉS DE UMA ETIQUETA
FIXADA NO NO ESPELHO DAS MESMAS.
CONDUTORES: NEUTRO, RETORNO, FASE E
TERRA, RESPECTIVAMENTE.
ELETRODUTO NO ENTREFORRO
TOMADA 2P+T 10A PADRÃO BRASILEIRO
INSTALADA EM CAIXA 2X4"; (PROX. AO
FORRO), ADICIONADAS.
CONJUNTO DE DUAS TOMADAS 2P+T 10A
PADRÃO BRASILEIRO INSTALADA EM CAIXA
4X4"; (PROX. AO FORRO), ADICIONADAS.
CANALETA INSTALADA NA PAREDE PRÓXIMO
AO RODAPÉ
CAIXA DE LIGAÇÃO PARA ELETRODUTO
(CONDULETE)
QUADRO DE DISTRIBUIÇÃO DE CIRCUITOS
(QDC)
RACK
L1a L1a L1a
L1b L1b L1b
L1b L1b L1b
L1c L1c L1c
L1c L1c L1c
ECTE03-10ECTE03-10
ECTE03-10
ECTE03-10 ECTE03-10 ECTE03-10
ECTE03-11 ECTE03-11 ECTE03-11
ECTE03-11 ECTE03-11ECTE03-11
ECTE03-11 ECTE03-11 ECTE03-11
ECTE03-11 ECTE03-11 ECTE03-11
4X16W
LUMINÁRIA
EXISTENTE
RELOCADA
REMOVER
2#2,5mm²
20A
A
ILUMINAÇÃO
AUDITÓRIO
EC
TE
03-10
2#2,5mm²
20A
B
ILUMINAÇÃO
AUDITÓRIO
EC
TE
03-11
ECTE03-10a
L1a L1a L1a
INTERRUPTOR
EXISTENTE SERÁ
RELOCADO
EXISTENTE
ECTE03-10bc
L1 - Luminária AR70 24º
0103
AUDITÓRIO
PROJETOR
EXISTENTE
PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
MINI RACK DE TELECOMUNICAÇÕES DE PAREDE
CAIXA DE LIGAÇÃO PARA ELETRODUTO (CONDULETE)
ELETRODUTO NO ENTREFORRO.
TOMADA RJ-45 CAT. 6 INSTALADA EM CAIXA 2X4"; (PROX. AO FORRO),
ADICIONADAS.
ELETRODUTO ABAIXO DO PISO ELEVADO ('ENTREPISOS').
CONJUNTO DE 2 TOMADAS RJ-45 CAT.6 INSTALADAS EM CAIXA 4X4"
CANALETAS DE 3 SEPTOS INSTALADAS NAS MESAS PARA PASSAGEM
DOS CABOS DE ELÉTRICA ESTABILIZADA, TELECOM. E SONORIZAÇÃO.
04xUTP4P
01-04
INDICAÇÃO DE QUANTIDADE DE CABOS UTPS PASSANDO EM
ELETRODUTO E INDENTIFICAÇÃO DO NÚMERO DOS PONTOS.
8 - OS PONTOS NÃO PODERÃO SER DESCONECTADOS DAS TOMADAS E NÃO SOFRERÃO
QUALQUER TIPO DE ALTERAÇÃO DEVIDO À REDE SER CERTIFICADA E POSSUIR GARANTIA
DO FORNECEDOR.
9- A TOMADA "TEA-C21" (EXISTENTE) SERÁ CONECTADA À UMA SWITCH PARA ORIGINAR
OS NOVOS PONTOS NECESSÁRIOS.
1 - ELETRODUTOS NÃO ESPECIFICADOS A SEREM INSTALADOS DEVERÃO SER DE AÇO
GALVANIZADO Ø3/4", AS CONEXÕES (CURVAS E LUVAS) DEVERÃO TER AS MESMAS
CARACTERÍSTICAS;
2 - DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE ACABAMENTO EM TODAS AS
EXTREMIDADES DOS ELETRODUTOS.
3 - TODOS OS CABOS UTP'S INSTALADOS DEVRÃO SER DE CATEORIA 6 FURUKAWA.
4 - TODOS OS CABOS DEVERÃO SER IDENTIFICADOS COM ANILHAS NO INICIO E FINAL, NAS
CAIXAS DE PASSAGEM E PONTOS DE SAÍDA.
5 - AS TOMADAS RJ-45 PARA SAÍDA DE DADOS OU VOZ DEVERÃO SER IDENTIFICADAS COM
ETIQUETA ADESIVA CONTENDO A NUMERAÇÃO DOS PONTOS DE ACORDO COM O
PROJETO.
6 - TODAS AS PORTAS DA SWITCH DEVERÃO SER IDENTIFICADAS.
7 - TODOS OS CABOS DEVERÃO SER TESTADOS E CERTIFICADOS EM CATEGORIA 6.
TOMADA RJ-45 CAT.6 EXISTENTE
TOMADA RJ45
EXISTENTE
TOMADA RJ45
EXISTENTE
TOMADA RJ45
EXISTENTE
A TOMADA "TEA-C21" (EXISTENTE)
SERÁ CONECTADA À UMA SWITCH
PARA ORIGINAR OS NOVOS PONTOS
NECESSÁRIOS.
U1
U2
U3
U4
U5
U6
RÉGUA DE (08) OITO TOMADAS
2P+T/15A (NO FUNDO DO RACK)
SWITCH 24 PORTAS (STE-01)
GUIA FRONTAL PARA CABOS
CP
STE1-01
STE1-02
STE1-03
STE1-04
RACK
STE-01
05xUTP4P
01-05
01xUTP4P
TEA-C21
STE1-05
STE1-06
STE1-07
0203
PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
CAIXA DE LIGAÇÃO PARA ELETRODUTO (CONDULETE)
ELETRODUTO NO ENTREFORRO.
CAIXAS DE SOM.
1 - ELETRODUTOS NÃO ESPECIFICADOS A SEREM INSTALADOS
DEVERÃO SER DE AÇO GALVANIZADO Ø3/4", AS CONEXÕES (CURVAS E
LUVAS) DEVERÃO TER AS MESMAS CARACTERÍSTICAS;
2 - DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE
ACABAMENTO EM TODAS AS EXTREMIDADES DOS ELETRODUTOS.
3 - TODOS OS CABOS DEVERÃO SER IDENTIFICADOS COM ANILHAS NO
INICIO E FINAL, NAS CAIXAS DE PASSAGEM E PONTOS DE SAÍDA.
4 - OS CABOS INSTALADOS NO 'ENTREPISOS' SERÃO ORGANIZADOS
ATRAVÉS DE ESPIRAL ORGANIZADORA DE CABOS.
5 - OS EQUIPAMENTOS DE SONORIZAÇÃO SÃO EXISTENTES.
6 - A ESPECIFICAÇÕES DOS COMPONENTES PODE SER ALTERADA
PARA ADEQUAÇÃO AOS EQUIPAMENTOS.
ELETRODUTO ABAIXO DO PISO ELEVADO ('ENTREPISOS').
PONTOS DE MICROFONE
CANALETAS DE 3 SEPTOS INSTALADAS NAS MESAS PARA
PASSAGEM DOS CABOS DE ELÉTRICA ESTABILIZADA,
TELECOM. E SONORIZAÇÃO.
INDICAÇÃO DE QUANTIDADE DE CABOS PORALIZADOS EM
ELETRODUTO E INDENTIFICAÇÃO DAS CAIXAS.
MI-01
CS-01
CS-02
CS-03
CS-04
CS-05
CS-06
RACK
0303
0102
PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
VEM DO QDE-02
2#2,5mm²
20A
A
32A
4#6,0mm²
CA#6,0mm²
RE
SE
RV
A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
RE
SE
RV
A
RE
SE
RV
A
VEM DO QDE-2
10- ELETRODUTOS NÃO COTADOS DEVERÃO SER DE Ø3/4".
FASE C ... BRANCA
NEUTRO ... AZUL
FASE A ... PRETO
RETORNO... CINZA
FASE B... VERMELHA
TERRA ... VERDE/AMARELA
2-CONDUTORES NÃO ESPECIFICADOS SERÃO EM COBRE, FLEXÍVEL, COM DUPLA CAMADA DE
ISOLAMENTO EM PVC, 750V, SEÇÃO MÍNIMA #2,5mm². TODOS OS CABOS DEVERÃO SER DO TIPO NÃO
PROPAGANTE À CHAMA, COM AUTO-EXTINÇÃO DO FOGO, CONSTATADO ATRAVÉS DE ENSAIOS,
POSSUÍREM PROPRIEDADES EXCLUSIVAS DE BAIXA EMISSÃO DE FUMAÇA E GASES TÓXICOS. REF.:
AFUMEX PRYSMIAN;
11-SONDAR TODOS OS ELETRODUTOS PREVIAMENTE, COM ARAME GALVANIZADO N°14 BWG PARA
PERMITIR A CORRETA PASSAGEM DOS CABOS;
12-AS EMENDAS, QUANDO NECESSÁRIAS, DEVERÃO SER SEMPRE FEITAS NO INTERIOR DAS CAIXAS
DE PASSAGEM, DEVENDO SER ISOLADAS COM FITA DE AUTO FUSÃO E FITA CONVENCIONAL;
14-DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE ACABAMENTO EM TODAS AS
EXTREMIDADES DE ELETRODUTOS, EXCETO NOS QUE TERMINAM EM CAIXAS DE SAÍDA.
6-ISOLAR O CONECTOR DE DERIVAÇÃO COM FITA AUTO-FUSÃO E CONVENCIONAL. O CABO PRINCIPAL
NÃO DEVERÁ SER SECCIONADO NO PONTO DE DERIVAÇÃO;
16-OS DISJUNTORES DEVERÃO SER IDENTIFICADOS ATRAVÉS DE PLACAS ACRÍLICAS E A
FIXAÇÃO DESTES DISJUNTORES SERÁ POR ENGATE RÁPIDO EM TRILHO DIN;
5-NA DISTRIBUIÇÃO DE QUALQUER CIRCUITO, OS CABOS NEUTRO E TERRA DEVERÃO SER
EXCLUSIVOS, NÃO SENDO ACEITOS TERRA OU NEUTRO COMUNS A OUTROS CIRCUITOS;
3 - TODOS OS CABOS DEVERÃO SER ANILHADOS (IDENTIFICAÇÃO DOS CABOS) EM TODAS AS CAIXAS,
CAIXAS DE PASSAGEM E/OU CONDULETES.
1 - COTAS EM MILÍMETROS, EXCETO ONDE INDICADO. COTAS PRIORITÁRIAS EM RELAÇÃO À ESCALA.
9- TODOS OS ELETRODUTOS OU TRECHOS DE ELETRODUTOS APARENTES OU NO INTERIOR DE
ESPAÇOS DE CONSTRUÇÃO ( ENTREFORRO, SHAFT) DEVERÃO UTILIZAR ELETRODUTOS DO TIPO
LEVE DE AÇO GALVANIZADO ELETROLITICAMENTE, CONFORME NBR 13.057.
13- OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE DUAS
CURVAS, EVITANDO-SE TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL.
7- TODAS AS CONEXÕES DE CONDUTORES ENTRE SI E COM OUTROS COMPONENTES DA
INSTALAÇÃO, DEVEM GARANTIR CONTINUIDADE ELÉTRICA DURÁVEL E ADEQUADA SUPORTABILIDADE
E PROTEÇÃO MECÂNICA. DEVERÃO ADEQUADAS SER APLICADAS COM FERRAMENTAS
8- ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO ATRAVÉS DO CABO
DE PROTEÇÃO Pe (TERRA) MAIS PRÓXIMO.
17- TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60 947-2
COM CURVAS DE ATUAÇÃO TIPO "B", "C", OU "D", CONFORME INDICAÇÃO.
18- O QUADRO SERÁ DE MATERIAL ISOLANTE , DE EMBUTIR (CONFORME PROJETO) , COM NO
MÍNIMO IP-30, PROVIDO DE ALETAS PARA VENTILAÇÃO E PORTA COM CHAVE E TRINCO,
DEVENDO POSSUIR, SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO NBR IEC 60439,
EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS.
19 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS
ATRAVÉS DE ETIQUETAS ACRÍLICAS, CONFORME NOMES DOS CIRCUITOS CONSTANTES NO
QUADRO DE CARGAS CORRESPONDENTE.
20 - ATERRAR TODAS AS PARTES METÁLICAS DOS QUADROS ATRAVÉS DE CABO DE COBRE
ISOLAÇÃO VERDE, EM PVC 70°C 750V.
21- O QUADRO DEVERÁ POSSUIR IDENTIFICAÇÃO DO QUADRO, TENSÃO E FREQUÊNCIA NA
FACE EXTERNA DE SUA PORTA, EM ETIQUETA INDELÉVEL DE FUNDO PRETO E LETRAS
BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO QUADRO.
22- O QUADRO DEVERÁ POSSUIR ETIQUETA ACRÍLICA DE IDENTIFICAÇÃO DOS CIRCUITOS E
FECHADURA E TER SEU DIAGRAMA AFIXADO EM SUA PORTA (INTERNAMENTE),
23- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE
COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE
FUMAÇA 70 ºC 750V.
24 - TODOS OS CABOS NO INTERIOR DO QUADRO DEVERÃO RECEBER ETIQUETAS DE
IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO A QUE ESTÁ LIGADO
25 - EM TODOS OS QUADROS (QDC'S) APRESENTADOS NESSE PROJETO, FORAM PREVISTOS
ESPAÇOS RESERVAS MÍNIMOS CONFORME NBR 5410 PARA AMPLIAÇÕES FUTURAS, COM BASE
NO NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADOS.
26 - DEVERÃO SER PREVISTAS CANALETAS DISTRIBUÍDAS NO INTERIOR DO QUADRO ELÉTRICO
PARA A PASSAGEM DOS CABOS DOS CIRCUITOS TERMINAIS. É IMPORTANTE SALIENTAR QUE
DEVERÁ SER RESPEITADA A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS NESSAS CANALETAS,
SEGUNDO ORIENTAÇOES DA NBR 5410/2004.
4 - OS CONDUTORES SERÃO IDENTIFICADOS PELA COR DE SEU ISOLAMENTO CONFORME SEGUE:
15- TODAS AS TOMADAS DEVERÃO SER IDENTIFICADAS ATRAVÉS DE UMA ETIQUETA FIXADA NO
NO ESPELHO DAS MESMAS.
CONDUTORES: NEUTRO, RETORNO,
FASE E TERRA, RESPECTIVAMENTE.
ELETRODUTO NO ENTREFORRO
TOMADA 2P+T 10A PADRÃO
BRASILEIRO INSTALADA EM CAIXA
2X4"; (PROX. AO FORRO),
ADICIONADAS.
CONJUNTO DE DUAS TOMADAS
2P+T 10A PADRÃO BRASILEIRO
INSTALADA EM CAIXA 4X4"; (PROX.
AO FORRO), ADICIONADAS.
CANALETA INSTALADA NA
PAREDE PRÓXIMO AO RODAPÉ
CAIXA DE LIGAÇÃO PARA
ELETRODUTO (CONDULETE)
QUADRO DE DISTRIBUIÇÃO DE
CIRCUITOS (QDC)
0202
PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
RACK
SWITCH
2-02
PTS2-01
PTS2-02
PTS2-03
PTS2-04
PTS2-05
PTS2-06
PTS2-07
PTS2-08
PTS2-09
PTS2-10
PTS2-11
PTS2-12
PTS2-13
PTS2-14
PTS2-15
PTS2-16
PTS2-17
PTS2-18
PTS2-19
PTS2-20
PTS2-21
PTS2-22
PTS2-23
PTS2-24
PTS2-25
PTS2-26
PTS2-27
PTS2-28
PTS2-29
PTS2-30
PTS2-31
PTS2-32
PTS2-33
PTS2-34
PTS2-35
PTS2-36
04xUTP4P
09-12
06xUTP4P
01-06
04xUTP4P
13-16
06xUTP4P
29-34
08xUTP4P
21-28
06xUTP4P
17-20 35 36
8 - OS PONTOS NÃO PODERÃO SER DESCONECTADOS DAS TOMADAS E NÃO SOFRERÃO
QUALQUER TIPO DE ALTERAÇÃO DEVIDO À REDE SER CERTIFICADA E POSSUIR GARANTIA
DO FORNECEDOR.
9 - AS TOMADAS "2A-D07" E "2A-D08" (EXISTENTES) SERÃO CONECTADAS À UMA SWITCH
CADA PARA ORIGINAR OS NOVOS PONTOS NECESSÁRIOS.
MINI RACK DE TELECOMUNICAÇÕES DE PAREDE
CAIXA DE LIGAÇÃO PARA ELETRODUTO (CONDULETE)
ELETRODUTO NO ENTREFORRO.
TOMADA RJ-45 CAT. 6 INSTALADA EM CAIXA 2X4"; (PROX. AO
FORRO), ADICIONADAS.
1 - ELETRODUTOS NÃO ESPECIFICADOS A SEREM INSTALADOS DEVERÃO SER DE AÇO
GALVANIZADO Ø3/4", AS CONEXÕES (CURVAS E LUVAS) DEVERÃO TER AS MESMAS
CARACTERÍSTICAS;
2 - DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE ACABAMENTO EM TODAS AS
EXTREMIDADES DOS ELETRODUTOS.
3 - TODOS OS CABOS UTP'S INSTALADOS DEVRÃO SER DE CATEORIA 6 FURUKAWA.
4 - TODOS OS CABOS DEVERÃO SER IDENTIFICADOS COM ANILHAS NO INICIO E FINAL, NAS
CAIXAS DE PASSAGEM E PONTOS DE SAÍDA.
5 - AS TOMADAS RJ-45 PARA SAÍDA DE DADOS OU VOZ DEVERÃO SER IDENTIFICADAS COM
ETIQUETA ADESIVA CONTENDO A NUMERAÇÃO DOS PONTOS DE ACORDO COM O
PROJETO.
6 - TODAS AS PORTAS DA SWITCH DEVERÃO SER IDENTIFICADAS.
7 - TODOS OS CABOS DEVERÃO SER TESTADOS E CERTIFICADOS EM CATEGORIA 6.
ELETRODUTO ABAIXO DO PISO ELEVADO ('ENTREPISOS').
CONJUNTO DE 2 TOMADAS RJ-45 CAT.6 INSTALADAS EM CAIXA
4X4" EM CANALETAS NAS MESAS.
CANALETAS DE 3 SEPTOS INSTALADAS NAS MESAS PARA
PASSAGEM DOS CABOS DE ELÉTRICA ESTABILIZADA, TELECOM.
E SONORIZAÇÃO.
04xUTP4P
01-04
INDICAÇÃO DE QUANTIDADE DE CABOS UTPS PASSANDO EM
ELETRODUTO E INDENTIFICAÇÃO DO NÚMERO DOS PONTOS.
U1
U2
U3
U4
U5
U6
RÉGUA DE (08) OITO
TOMADAS 2P+T/15A
(NO FUNDO DO RACK)
SWITCH 24 PORTAS
GUIA FRONTAL
PARA CABOS
02xUTP4P
07-08
AS TOMADAS "2A-D07" E "2A-D08" (EXISTENTES)
SERÃO CONECTADAS À UMA SWITCH CADA PARA
ORIGINAR OS NOVOS PONTOS NECESSÁRIOS.
U7
U8
CP
S
0102
PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
P1 - Perfil ML 19,2W linear EF52-E
(L=4 ou 7cm), conforme projeto.
T1 - trilho padrão existente
S1 - Novo spot - PAR20
L1 - Luminária AR70 24º
S2 - Novo spot - AR70 12º
COLOCAR TAMPA CEGA NA CAIXA DE
PISO EXISTENTE.
QDC-1
(EXISTENTE)
MANTER O TRILHO
EXISTENTE PARA
INTERLIGAR AO
NOVO TRILHO
INTERLIGAR OS TRILHOS
UTILIZANDO PLASTICHUMBO
INTERLIGAR OS TRILHOS
UTILIZANDO PLASTICHUMBO
QUADRO DE DISTRIBUIÇÃO DE CIRCUITOS (QDC)
CAIXA DE LIGAÇÃO PARA ELETRODUTO (CONDULETE)
CONDUTORES: NEUTRO, RETORNO, FASE E TERRA,
RESPECTIVAMENTE.
ELETRODUTO NO ENTREFORRO
TOMADA 2P+T 10A PADRÃO BRASILEIRO INSTALADA EM
CAIXA 2X4"; (PROX. AO FORRO), ADICIONADAS.
CCTE1-29ab
CCTE1-29a
CCTE1-29b
CCTE1-30
220V
CCTE1-31
CCTE1-32
T1.1
10- ELETRODUTOS NÃO COTADOS DEVERÃO SER DE Ø3/4".
FASE C ... BRANCA
NEUTRO ... AZUL
FASE A ... PRETO
RETORNO... CINZA
FASE B... VERMELHA
TERRA ... VERDE/AMARELA
2-CONDUTORES NÃO ESPECIFICADOS SERÃO EM COBRE, FLEXÍVEL, COM DUPLA CAMADA DE
ISOLAMENTO EM PVC, 750V, SEÇÃO MÍNIMA #2,5mm². TODOS OS CABOS DEVERÃO SER DO TIPO NÃO
PROPAGANTE À CHAMA, COM AUTO-EXTINÇÃO DO FOGO, CONSTATADO ATRAVÉS DE ENSAIOS,
POSSUÍREM PROPRIEDADES EXCLUSIVAS DE BAIXA EMISSÃO DE FUMAÇA E GASES TÓXICOS. REF.:
AFUMEX PRYSMIAN;
11-SONDAR TODOS OS ELETRODUTOS PREVIAMENTE, COM ARAME GALVANIZADO N°14 BWG PARA
PERMITIR A CORRETA PASSAGEM DOS CABOS;
12-AS EMENDAS, QUANDO NECESSÁRIAS, DEVERÃO SER SEMPRE FEITAS NO INTERIOR DAS CAIXAS
DE PASSAGEM, DEVENDO SER ISOLADAS COM FITA DE AUTO FUSÃO E FITA CONVENCIONAL;
14-DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE ACABAMENTO EM TODAS AS
EXTREMIDADES DE ELETRODUTOS, EXCETO NOS QUE TERMINAM EM CAIXAS DE SAÍDA.
6-ISOLAR O CONECTOR DE DERIVAÇÃO COM FITA AUTO-FUSÃO E CONVENCIONAL. O CABO PRINCIPAL
NÃO DEVERÁ SER SECCIONADO NO PONTO DE DERIVAÇÃO;
16-OS DISJUNTORES DEVERÃO SER IDENTIFICADOS ATRAVÉS DE PLACAS ACRÍLICAS E A
FIXAÇÃO DESTES DISJUNTORES SERÁ POR ENGATE RÁPIDO EM TRILHO DIN;
5-NA DISTRIBUIÇÃO DE QUALQUER CIRCUITO, OS CABOS NEUTRO E TERRA DEVERÃO SER
EXCLUSIVOS, NÃO SENDO ACEITOS TERRA OU NEUTRO COMUNS A OUTROS CIRCUITOS;
3 - TODOS OS CABOS DEVERÃO SER ANILHADOS (IDENTIFICAÇÃO DOS CABOS) EM TODAS AS CAIXAS,
CAIXAS DE PASSAGEM E/OU CONDULETES.
1 - COTAS EM MILÍMETROS, EXCETO ONDE INDICADO. COTAS PRIORITÁRIAS EM RELAÇÃO À ESCALA.
9- TODOS OS ELETRODUTOS OU TRECHOS DE ELETRODUTOS APARENTES OU NO INTERIOR DE
ESPAÇOS DE CONSTRUÇÃO ( ENTREFORRO, SHAFT) DEVERÃO UTILIZAR ELETRODUTOS DO TIPO
LEVE DE AÇO GALVANIZADO ELETROLITICAMENTE, CONFORME NBR 13.057.
13- OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE DUAS
CURVAS, EVITANDO-SE TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL.
7- TODAS AS CONEXÕES DE CONDUTORES ENTRE SI E COM OUTROS COMPONENTES DA
INSTALAÇÃO, DEVEM GARANTIR CONTINUIDADE ELÉTRICA DURÁVEL E ADEQUADA SUPORTABILIDADE
E PROTEÇÃO MECÂNICA. DEVERÃO ADEQUADAS SER APLICADAS COM FERRAMENTAS
8- ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO ATRAVÉS DO CABO
DE PROTEÇÃO Pe (TERRA) MAIS PRÓXIMO.
17- TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60 947-2
COM CURVAS DE ATUAÇÃO TIPO "B", "C", OU "D", CONFORME INDICAÇÃO.
18- OS CIRCUITOS CCTE1-29/30/ 31/32 SRÃO RETIRADOS DO QDC-TE-1 EXISTENTE. O CIRCUITO
T1.1 É EXISTENTE NO QDC-1 DO MEMORIAL. A ALIMENTAÇÃO DOS NOVOS TRILHOS
ELETRIFICADOS SERÁ FEITA ATRAVÉS DE INTERLIGAÇÃO DOS TRILHOS EXISTENTES
UTILIZANDO-SE PLASTICHUMBO.
19 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS
ATRAVÉS DE ETIQUETAS ACRÍLICAS, CONFORME NOMES DOS CIRCUITOS CONSTANTES NO
QUADRO DE CARGAS CORRESPONDENTE.
20 - ATERRAR TODAS AS PARTES METÁLICAS DOS QUADROS ATRAVÉS DE CABO DE COBRE
ISOLAÇÃO VERDE, EM PVC 70°C 750V.
21- O QUADRO DEVERÁ POSSUIR IDENTIFICAÇÃO DO QUADRO, TENSÃO E FREQUÊNCIA NA
FACE EXTERNA DE SUA PORTA, EM ETIQUETA INDELÉVEL DE FUNDO PRETO E LETRAS
BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO QUADRO.
22- O QUADRO DEVERÁ POSSUIR ETIQUETA ACRÍLICA DE IDENTIFICAÇÃO DOS CIRCUITOS E
FECHADURA E TER SEU DIAGRAMA AFIXADO EM SUA PORTA (INTERNAMENTE),
23- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE
COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE
FUMAÇA 70 ºC 750V.
24 - TODOS OS CABOS NO INTERIOR DO QUADRO DEVERÃO RECEBER ETIQUETAS DE
IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO A QUE ESTÁ LIGADO
25 - EM TODOS OS QUADROS (QDC'S) APRESENTADOS NESSE PROJETO, FORAM PREVISTOS
ESPAÇOS RESERVAS MÍNIMOS CONFORME NBR 5410 PARA AMPLIAÇÕES FUTURAS, COM BASE
NO NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADOS.
26 - DEVERÃO SER PREVISTAS CANALETAS DISTRIBUÍDAS NO INTERIOR DO QUADRO ELÉTRICO
PARA A PASSAGEM DOS CABOS DOS CIRCUITOS TERMINAIS. É IMPORTANTE SALIENTAR QUE
DEVERÁ SER RESPEITADA A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS NESSAS CANALETAS,
SEGUNDO ORIENTAÇOES DA NBR 5410/2004.
4 - OS CONDUTORES SERÃO IDENTIFICADOS PELA COR DE SEU ISOLAMENTO CONFORME SEGUE:
15- TODAS AS TOMADAS DEVERÃO SER IDENTIFICADAS ATRAVÉS DE UMA ETIQUETA FIXADA NO
NO ESPELHO DAS MESMAS.
CCTE1-32
2#2,5mm²
20A
ILUMINAÇÃO
HA
LL
2#2,5mm²
20A
CA
TR
AC
AS
2#2,5mm²
20A
CC
TE
1-29
3#2,5mm²
20A
MÁQ DE CAFÉ
RECEPÇÃO
CC
TE
1-30
CC
TE
1-31
CC
TE
1-32
ø1"
S
0202
PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
8 - AS TOMADAS "1A-A20" A "1A-A23" SERÃO REMOVIDAS DA PAREDE JUNTAMENTE COM A
CANALETA E ACONDICIONADAS NA CAIXA DE PASSAGEM NO SHAFT.
9 - OS PONTOS NÃO PODERÃO SER DESCONECTADOS DAS TOMADAS E NÃO SOFRERÃO
QUALQUER TIPO DE ALTERAÇÃO DEVIDO À REDE SER CERTIFICADA E POSSUIR GARANTIA
DO FORNECEDOR.
10 - À TOMADA "1A-A20" SERÁ CONECTADA UMA SWITCH PARA ORIGINAR OS NOVOS
PONTOS NECESSÁRIOS.
11 - OS CABOS INSTALADOS NO 'ENTREPISOS' SERÃO ORGANIZADOS ATRAVÉS DE
ESPIRAL ORGANIZADORA DE CABOS.
MINI RACK DE TELECOMUNICAÇÕES DE PAREDE
CAIXA DE LIGAÇÃO PARA ELETRODUTO (CONDULETE)
ELETRODUTO NO ENTREFORRO.
TOMADA RJ-45 CAT. 6 INSTALADA EM CAIXA 2X4"; (PROX. AO
FORRO), ADICIONADAS.
1 - ELETRODUTOS NÃO ESPECIFICADOS A SEREM INSTALADOS DEVERÃO SER DE AÇO
GALVANIZADO Ø3/4", AS CONEXÕES (CURVAS E LUVAS) DEVERÃO TER AS MESMAS
CARACTERÍSTICAS;
2 - DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE ACABAMENTO EM TODAS AS
EXTREMIDADES DOS ELETRODUTOS.
3 - TODOS OS CABOS UTP'S INSTALADOS DEVRÃO SER DE CATEORIA 6 FURUKAWA.
4 - TODOS OS CABOS DEVERÃO SER IDENTIFICADOS COM ANILHAS NO INICIO E FINAL, NAS
CAIXAS DE PASSAGEM E PONTOS DE SAÍDA.
5 - AS TOMADAS RJ-45 PARA SAÍDA DE DADOS OU VOZ DEVERÃO SER IDENTIFICADAS COM
ETIQUETA ADESIVA CONTENDO A NUMERAÇÃO DOS PONTOS DE ACORDO COM O
PROJETO.
6 - TODAS AS PORTAS DA SWITCH DEVERÃO SER IDENTIFICADAS.
7 - TODOS OS CABOS DEVERÃO SER TESTADOS E CERTIFICADOS EM CATEGORIA 6.
ELETRODUTO ABAIXO DO PISO ELEVADO ('ENTREPISOS').
CONJUNTO DE 2 TOMADAS RJ-45 CAT.6 INSTALADAS EM CAIXA
4X4" EM CANALETAS NAS MESAS.
CANALETAS DE 3 SEPTOS INSTALADAS NAS MESAS PARA
PASSAGEM DOS CABOS DE ELÉTRICA ESTABILIZADA, TELECOM.
E SONORIZAÇÃO.
04xUTP4P
01-04
INDICAÇÃO DE QUANTIDADE DE CABOS UTPS PASSANDO EM
ELETRODUTO E INDENTIFICAÇÃO DO NÚMERO DOS PONTOS.
ø1"
07xUTP4P
09-15
STE1-08STE1-09
STE1-10
STE1-11
STE1-12
STE1-13
STE1-14
STE1-15
VEM DO RACK/SWITCH
STE01 (AUDITÓRIO)
06xUTP4P
10-15
RACK
SHAFT
EC102-01
EC102-02
EC102-01
EC102-02
EC102-03
PREVER CORTE NA ALTURA
DO PISO ELEVADO PARA
INTERLIGAR AO SHAFT
QDCEC1-02
QDCEE-01
CX PASSAGEM
ELETROCALHA EXISTENTE
VEM DO QGBT-1
TOMADA INSTALADA EM
CAIXA DE SOBREPOR
PRÓXIMA AO FORRO
0104
PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
2#2,5mm²
20A
A
32A
4#6,0mm²
CA#6,0mm²
RE
SE
RV
A
VE
NT
ILA
DO
RE
S
2#2,5mm²
20A
CA
IX
AS
D
E
SO
M
2#2,5mm²
20A
VE
NT
ILA
DO
RE
S
2#2,5mm²
20A
RE
SE
RV
A
CO
ND
. A
R
RE
SE
RV
A
CO
ND
. D
E A
R
RE
SE
RV
A
RE
SE
RV
A
VEM DO QGBT-1
2#2,5mm²
20A
10- ELETRODUTOS NÃO COTADOS DEVERÃO SER DE Ø3/4".
FASE C ... BRANCA
NEUTRO ... AZUL
FASE A ... PRETO
RETORNO... CINZA
FASE B... VERMELHA
TERRA ... VERDE/AMARELA
2-CONDUTORES NÃO ESPECIFICADOS SERÃO EM COBRE, FLEXÍVEL, COM DUPLA CAMADA
DE ISOLAMENTO EM PVC, 750V, SEÇÃO MÍNIMA #2,5mm². TODOS OS CABOS DEVERÃO SER
DO TIPO NÃO PROPAGANTE À CHAMA, COM AUTO-EXTINÇÃO DO FOGO, CONSTATADO
ATRAVÉS DE ENSAIOS, POSSUÍREM PROPRIEDADES EXCLUSIVAS DE BAIXA EMISSÃO DE
FUMAÇA E GASES TÓXICOS. REF.: AFUMEX PRYSMIAN;
11-SONDAR TODOS OS ELETRODUTOS PREVIAMENTE, COM ARAME GALVANIZADO N°14
BWG PARA PERMITIR A CORRETA PASSAGEM DOS CABOS;
12-AS EMENDAS, QUANDO NECESSÁRIAS, DEVERÃO SER SEMPRE FEITAS NO INTERIOR
DAS CAIXAS DE PASSAGEM, DEVENDO SER ISOLADAS COM FITA DE AUTO FUSÃO E FITA
CONVENCIONAL;
14-DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE ACABAMENTO EM TODAS AS
EXTREMIDADES DE ELETRODUTOS, EXCETO NAQUELES QUE TERMINAM EM CAIXAS DE
SAÍDA 2"x4" OU 4"x4";
6-ISOLAR O CONECTOR DE DERIVAÇÃO COM FITA AUTO-FUSÃO E CONVENCIONAL. O CABO
PRINCIPAL NÃO DEVERÁ SER SECCIONADO NO PONTO DE DERIVAÇÃO;
16-OS DISJUNTORES DEVERÃO SER IDENTIFICADOS ATRAVÉS DE PLACAS ACRÍLICAS E A
FIXAÇÃO DESTES DISJUNTORES SERÁ POR ENGATE RÁPIDO EM TRILHO DIN;
5-NA DISTRIBUIÇÃO DE QUALQUER CIRCUITO, OS CABOS NEUTRO E TERRA DEVERÃO SER
EXCLUSIVOS, NÃO SENDO ACEITOS TERRA OU NEUTRO COMUNS A OUTROS CIRCUITOS;
3 - TODOS OS CABOS DEVERÃO SER ANILHADOS (IDENTIFICAÇÃO DOS CABOS) EM TODAS
AS CAIXAS, CAIXAS DE PASSAGEM E/OU CONDULETES.
1 - COTAS EM MILÍMETROS, EXCETO ONDE INDICADO. CONSIDERAR AS COTAS
PRIORITÁRIAS EM RELAÇÃO À ESCALA.
9- TODOS OS ELETRODUTOS OU TRECHOS DE ELETRODUTOS APARENTES OU NO
INTERIOR DE ESPAÇOS DE CONSTRUÇÃO (POR EXEMPLO; ENTREFORRO, SHAFT)
DEVERÃO UTILIZAR ELETRODUTOS DO TIPO LEVE DE AÇO GALVANIZADO
ELETROLITICAMENTE, CONFORME NBR 13.057. NÃO UTILIZAR ELETRODUTOS DO TIPO
PESADOS NAS ÁREAS INTERNAS À EDIFICAÇÃO.
13- OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE
DUAS CURVAS, EVITANDO-SE TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL.
7- TODAS AS CONEXÕES DE CONDUTORES ENTRE SI E COM OUTROS COMPONENTES DA
INSTALAÇÃO, DEVEM GARANTIR CONTINUIDADE ELÉTRICA DURÁVEL E ADEQUADA
SUPORTABILIDADE E PROTEÇÃO MECÂNICA. DEVERÃO ADEQUADAS SER APLICADAS COM
FERRAMENTAS
8- ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO ATRAVÉS
DO CABO DE PROTEÇÃO Pe (TERRA) MAIS PRÓXIMO.
17- TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60
947-2 , COM CURVAS DE ATUAÇÃO TIPO "B", "C", OU "D", CONFORME INDICAÇÃO NO
QUADRO DE CARGAS CORRESPONDENTE
18- O QUADRO SERÁ DE MATERIAL ISOLANTE , DE EMBUTIR (CONFORME PROJETO) , COM
NO MÍNIMO IP-30, PROVIDO DE ALETAS PARA VENTILAÇÃO E PORTA COM CHAVE E
TRINCO, DEVENDO POSSUIR, SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO NBR IEC
60439, EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS.
19 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS
ATRAVÉS DE ETIQUETAS ACRÍLICAS, CONFORME NOMES DOS CIRCUITOS CONSTANTES
NO QUADRO DE CARGAS CORRESPONDENTE.
20 - ATERRAR TODAS AS PARTES METÁLICAS DOS QUADROS ATRAVÉS DE CABO DE
COBRE ISOLAÇÃO VERDE, EM PVC 70°C 750V.
21- O QUADRO DEVERÁ POSSUIR IDENTIFICAÇÃO DO QUADRO, TENSÃO E FREQUÊNCIA NA
FACE EXTERNA DE SUA PORTA, EM ETIQUETA INDELÉVEL DE FUNDO PRETO E LETRAS
BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO
QUADRO.
22- O QUADRO DEVERÁ POSSUIR ETIQUETA ACRÍLICA DE IDENTIFICAÇÃO DOS CIRCUITOS
E FECHADURA E TER SEU DIAGRAMA AFIXADO EM SUA PORTA (INTERNAMENTE),
23- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE
COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE
FUMAÇA 70 ºC 750V.
24 - TODOS OS CABOS NO INTERIOR DO QUADRO DEVERÃO RECEBER ETIQUETAS DE
IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO A QUE ESTÁ LIGADO
25 - EM TODOS OS QUADROS (QDC'S) APRESENTADOS NESSE PROJETO, FORAM
PREVISTOS ESPAÇOS RESERVAS MÍNIMOS CONFORME NBR 5410 PARA AMPLIAÇÕES
FUTURAS, COM BASE NO NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADOS.
26 - DEVERÃO SER PREVISTAS CANALETAS DISTRIBUÍDAS NO INTERIOR DO QUADRO
ELÉTRICO PARA A PASSAGEM DOS CABOS DOS CIRCUITOS TERMINAIS. É IMPORTANTE
SALIENTAR QUE DEVERÁ SER RESPEITADA A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS
NESSAS CANALETAS, SEGUNDO ORIENTAÇOES DA NBR 5410/2004.
27- TODOS OS QUADROS DEVERÃO ESTAR LIMPOS, LIVRES DE ARGAMASSAS, POEIRA,
CAPA DE CABOS, FILAMENTOS DE CABOS DE COBRE E OUTROS MATERIAIS ESTRANHOS À
INSTALAÇÃO.
4 - OS CONDUTORES DEVERÃO SER IDENTIFICADOS PELA COR DE SEU ISOLAMENTO
CONFORME SEGUE:
15- TODAS AS TOMADAS DEVERÃO SER IDENTIFICADAS ATRAVÉS DE UMA ETIQUETA
FIXADA NO NO ESPELHO DAS MESMAS.
QUADRO DE DISTRIBUIÇÃO DE CIRCUITOS (QDC)
CAIXA DE LIGAÇÃO PARA ELETRODUTO (CONDULETE)
CONDUTORES: NEUTRO, RETORNO, FASE E TERRA, RESPECTIVAMENTE.
ELETRODUTO NO ENTREFORRO
TOMADA 2P+T 10A PADRÃO BRASILEIRO INSTALADA EM CAIXA 2X4"; (PROX.
AO FORRO), ADICIONADAS.
B B BC AC
CX PASSAGEM
RELÓGIO
PREVER CORTE NA ALTURA
DO PISO ELEVADO PARA
INTERLIGAR AO SHAFT
SHAFT
PROJETOR
EE1-01
EE1-01
EE1-02EE1-02EE1-03
EE1-04EE1-04
EE1-05EE1-05
EE1-06
EE1-06
EE1-06
EE1-07
EE1-08
(CFTV)
EE1-07
EE1-09
EE1-10
VEM DO QDE-1
QDCEC1-02
QDCEE-01
ELETROCALHA EXISTENTE
0204
PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
2#2,5mm²
20A
A
32A
4#6,0mm²
CA#6,0mm²
RE
SE
RV
A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
ESTAÇÕES DE
TR
AB
ALH
O
2#2,5mm²
20A
PR
OJE
TO
R E
RE
LO
GIO
2#2,5mm²
20A
CÂMERA
CF
TV
2#2,5mm²
20A
RA
CK
D
E
TE
LE
CO
M.
RE
SE
RV
A
RE
SE
RV
A
VEM DO QDE-1
QUADRO DE DISTRIBUIÇÃO DE CIRCUITOS (QDC)
CAIXA DE LIGAÇÃO PARA ELETRODUTO (CONDULETE)
CONDUTORES: NEUTRO, RETORNO, FASE E TERRA, RESPECTIVAMENTE.
ELETRODUTO NO ENTREFORRO.
TOMADA 2P+T 10A PADRÃO BRASILEIRO INSTALADA EM CAIXA 2X4"; (PROX.
AO FORRO), ADICIONADAS.
10- ELETRODUTOS NÃO COTADOS DEVERÃO SER DE Ø3/4".
FASE C ... BRANCA
NEUTRO ... AZUL
FASE A ... PRETO
RETORNO... CINZA
FASE B... VERMELHA
TERRA ... VERDE/AMARELA
2-CONDUTORES NÃO ESPECIFICADOS SERÃO EM COBRE, FLEXÍVEL, COM DUPLA CAMADA
DE ISOLAMENTO EM PVC, 750V, SEÇÃO MÍNIMA #2,5mm². TODOS OS CABOS DEVERÃO SER
DO TIPO NÃO PROPAGANTE À CHAMA, COM AUTO-EXTINÇÃO DO FOGO, CONSTATADO
ATRAVÉS DE ENSAIOS, POSSUÍREM PROPRIEDADES EXCLUSIVAS DE BAIXA EMISSÃO DE
FUMAÇA E GASES TÓXICOS. REF.: AFUMEX PRYSMIAN;
11-SONDAR TODOS OS ELETRODUTOS PREVIAMENTE, COM ARAME GALVANIZADO N°14
BWG PARA PERMITIR A CORRETA PASSAGEM DOS CABOS;
12-AS EMENDAS, QUANDO NECESSÁRIAS, DEVERÃO SER SEMPRE FEITAS NO INTERIOR
DAS CAIXAS DE PASSAGEM, DEVENDO SER ISOLADAS COM FITA DE AUTO FUSÃO E FITA
CONVENCIONAL;
14-DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE ACABAMENTO EM TODAS AS
EXTREMIDADES DE ELETRODUTOS, EXCETO NAQUELES QUE TERMINAM EM CAIXAS DE
SAÍDA 2"x4" OU 4"x4";
6-ISOLAR O CONECTOR DE DERIVAÇÃO COM FITA AUTO-FUSÃO E CONVENCIONAL. O CABO
PRINCIPAL NÃO DEVERÁ SER SECCIONADO NO PONTO DE DERIVAÇÃO;
16-OS DISJUNTORES DEVERÃO SER IDENTIFICADOS ATRAVÉS DE PLACAS ACRÍLICAS E A
FIXAÇÃO DESTES DISJUNTORES SERÁ POR ENGATE RÁPIDO EM TRILHO DIN;
5-NA DISTRIBUIÇÃO DE QUALQUER CIRCUITO, OS CABOS NEUTRO E TERRA DEVERÃO SER
EXCLUSIVOS, NÃO SENDO ACEITOS TERRA OU NEUTRO COMUNS A OUTROS CIRCUITOS;
3 - TODOS OS CABOS DEVERÃO SER ANILHADOS (IDENTIFICAÇÃO DOS CABOS) EM TODAS
AS CAIXAS, CAIXAS DE PASSAGEM E/OU CONDULETES.
1 - COTAS EM MILÍMETROS, EXCETO ONDE INDICADO. CONSIDERAR AS COTAS
PRIORITÁRIAS EM RELAÇÃO À ESCALA.
9- TODOS OS ELETRODUTOS OU TRECHOS DE ELETRODUTOS APARENTES OU NO
INTERIOR DE ESPAÇOS DE CONSTRUÇÃO (POR EXEMPLO; ENTREFORRO, SHAFT)
DEVERÃO UTILIZAR ELETRODUTOS DO TIPO LEVE DE AÇO GALVANIZADO
ELETROLITICAMENTE, CONFORME NBR 13.057. NÃO UTILIZAR ELETRODUTOS DO TIPO
PESADOS NAS ÁREAS INTERNAS À EDIFICAÇÃO.
13- OS LANCES ENTRE DUAS CAIXAS DE PASSAGEM NÃO DEVERÃO CONTER MAIS DO QUE
DUAS CURVAS, EVITANDO-SE TAMBÉM CURVAS REVERSAS SEMPRE QUE POSSÍVEL.
7- TODAS AS CONEXÕES DE CONDUTORES ENTRE SI E COM OUTROS COMPONENTES DA
INSTALAÇÃO, DEVEM GARANTIR CONTINUIDADE ELÉTRICA DURÁVEL E ADEQUADA
SUPORTABILIDADE E PROTEÇÃO MECÂNICA. DEVERÃO ADEQUADAS SER APLICADAS COM
FERRAMENTAS
8- ATERRAR TODAS AS PARTES METÁLICAS NÃO ENERGIZADAS DA INSTALAÇÃO ATRAVÉS
DO CABO DE PROTEÇÃO Pe (TERRA) MAIS PRÓXIMO.
17- TODOS OS DISJUNTORES DOS CIRCUITOS TERMINAIS OBEDECERÃO À NBR IEC-60
947-2 , COM CURVAS DE ATUAÇÃO TIPO "B", "C", OU "D", CONFORME INDICAÇÃO NO
QUADRO DE CARGAS CORRESPONDENTE
18- O QUADRO SERÁ DE MATERIAL ISOLANTE , DE EMBUTIR (CONFORME PROJETO) , COM
NO MÍNIMO IP-30, PROVIDO DE ALETAS PARA VENTILAÇÃO E PORTA COM CHAVE E
TRINCO, DEVENDO POSSUIR, SOBRETUDO, CERTIFICAÇÃO DE TESTES SEGUNDO NBR IEC
60439, EMITIDO POR EMPRESA ESPECIALIZADA NA MONTAGEM DE QUADROS ELÉTRICOS.
19 - TODOS OS DISJUNTORES NO INTERIOR DOS QUADROS DEVERÃO SER IDENTIFICADOS
ATRAVÉS DE ETIQUETAS ACRÍLICAS, CONFORME NOMES DOS CIRCUITOS CONSTANTES
NO QUADRO DE CARGAS CORRESPONDENTE.
20 - ATERRAR TODAS AS PARTES METÁLICAS DOS QUADROS ATRAVÉS DE CABO DE
COBRE ISOLAÇÃO VERDE, EM PVC 70°C 750V.
21- O QUADRO DEVERÁ POSSUIR IDENTIFICAÇÃO DO QUADRO, TENSÃO E FREQUÊNCIA NA
FACE EXTERNA DE SUA PORTA, EM ETIQUETA INDELÉVEL DE FUNDO PRETO E LETRAS
BRANCAS. TAMBÉM DEVERÁ POSSUIR UMA PLACA DE ADVERTÊNCIA INTERNA AO
QUADRO.
22- O QUADRO DEVERÁ POSSUIR ETIQUETA ACRÍLICA DE IDENTIFICAÇÃO DOS CIRCUITOS
E FECHADURA E TER SEU DIAGRAMA AFIXADO EM SUA PORTA (INTERNAMENTE),
23- TODOS OS CABOS ALIMENTADORES DOS CIRCUITOS INTERNOS AO QUADRO SERÃO DE
COBRE COM ISOLAÇÃO TERMOPLÁSTICO NÃO HALOGENADO E COM BAIXA EMISSÃO DE
FUMAÇA 70 ºC 750V.
24 - TODOS OS CABOS NO INTERIOR DO QUADRO DEVERÃO RECEBER ETIQUETAS DE
IDENTIFICAÇÃO (TAG´s), INDELÉVEIS, COM INDICAÇÃO DO CIRCUITO A QUE ESTÁ LIGADO
25 - EM TODOS OS QUADROS (QDC'S) APRESENTADOS NESSE PROJETO, FORAM
PREVISTOS ESPAÇOS RESERVAS MÍNIMOS CONFORME NBR 5410 PARA AMPLIAÇÕES
FUTURAS, COM BASE NO NÚMERO DE CIRCUITOS EFETIVAMENTE INSTALADOS.
26 - DEVERÃO SER PREVISTAS CANALETAS DISTRIBUÍDAS NO INTERIOR DO QUADRO
ELÉTRICO PARA A PASSAGEM DOS CABOS DOS CIRCUITOS TERMINAIS. É IMPORTANTE
SALIENTAR QUE DEVERÁ SER RESPEITADA A TAXA DE OCUPAÇÃO MÁXIMA DOS CABOS
NESSAS CANALETAS, SEGUNDO ORIENTAÇOES DA NBR 5410/2004.
27- TODOS OS QUADROS DEVERÃO ESTAR LIMPOS, LIVRES DE ARGAMASSAS, POEIRA,
CAPA DE CABOS, FILAMENTOS DE CABOS DE COBRE E OUTROS MATERIAIS ESTRANHOS À
INSTALAÇÃO.
28- OS CABOS INSTALADOS NO 'ENTREPISOS' SERÃO ORGANIZADOS ATRAVÉS DE ESPIRAL
ORGANIZADORA DE CABOS.
4 - OS CONDUTORES DEVERÃO SER IDENTIFICADOS PELA COR DE SEU ISOLAMENTO
CONFORME SEGUE:
15- TODAS AS TOMADAS DEVERÃO SER IDENTIFICADAS ATRAVÉS DE UMA ETIQUETA
FIXADA NO NO ESPELHO DAS MESMAS.
ELETRODUTO ABAIXO DO PISO ELEVADO ('ENTREPISOS').
CONJUNTO DE 2 TOMADAS 2P+T 10A PADRÃO BRASILEIRO INSTALADA EM
CAIXA 4X4" EM CANALETAS NAS MESAS.
CANALETAS DE 3 SEPTOS INSTALADAS NAS MESAS PARA PASSAGEM
DOS CABOS DE ELÉTRICA ESTABILIZADA, TELECOM. E SONORIZAÇÃO.
PTS1-01
8 - AS TOMADAS "1A-A20" A "1A-A23" SERÃO REMOVIDAS DA PAREDE JUNTAMENTE COM A
CANALETA E ACONDICIONADAS NA CAIXA DE PASSAGEM NO SHAFT.
9 - OS PONTOS NÃO PODERÃO SER DESCONECTADOS DAS TOMADAS E NÃO SOFRERÃO
QUALQUER TIPO DE ALTERAÇÃO DEVIDO À REDE SER CERTIFICADA E POSSUIR GARANTIA
DO FORNECEDOR.
10 - À TOMADA "1A-A20" SERÁ CONECTADA UMA SWITCH PARA ORIGINAR OS NOVOS
PONTOS NECESSÁRIOS.
11 - OS CABOS INSTALADOS NO 'ENTREPISOS' SERÃO ORGANIZADOS ATRAVÉS DE
ESPIRAL ORGANIZADORA DE CABOS.
PTS1-02
PTS1-03
PTS1-04
PTS1-05
PTS1-06
PTS1-07
PTS1-08
PTS1-09
PTS1-10
PTS1-11
PTS1-12
PTS1-13
PTS1-14
PTS1-15
PTS1-16
PTS1-17
PTS1-18
PTS1-19
PTS1-20
PTS1-21
PTS1-22
18xUTP4P
05-22
04xUTP4P
01-04
PTS1-23
1xUTP4P
23
QDCEC1-02
QDCEE-01
ELETROCALHA EXISTENTE
0304
PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
MINI RACK DE TELECOMUNICAÇÕES DE PAREDE
CAIXA DE LIGAÇÃO PARA ELETRODUTO (CONDULETE)
ELETRODUTO NO ENTREFORRO.
TOMADA RJ-45 CAT. 6 INSTALADA EM CAIXA 2X4"; (PROX. AO FORRO),
ADICIONADAS.
1 - ELETRODUTOS NÃO ESPECIFICADOS A SEREM INSTALADOS DEVERÃO SER DE AÇO
GALVANIZADO Ø3/4", AS CONEXÕES (CURVAS E LUVAS) DEVERÃO TER AS MESMAS
CARACTERÍSTICAS;
2 - DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE ACABAMENTO EM TODAS AS
EXTREMIDADES DOS ELETRODUTOS.
3 - TODOS OS CABOS UTP'S INSTALADOS DEVRÃO SER DE CATEORIA 6 FURUKAWA.
4 - TODOS OS CABOS DEVERÃO SER IDENTIFICADOS COM ANILHAS NO INICIO E FINAL, NAS
CAIXAS DE PASSAGEM E PONTOS DE SAÍDA.
5 - AS TOMADAS RJ-45 PARA SAÍDA DE DADOS OU VOZ DEVERÃO SER IDENTIFICADAS COM
ETIQUETA ADESIVA CONTENDO A NUMERAÇÃO DOS PONTOS DE ACORDO COM O
PROJETO.
6 - TODAS AS PORTAS DA SWITCH DEVERÃO SER IDENTIFICADAS.
7 - TODOS OS CABOS DEVERÃO SER TESTADOS E CERTIFICADOS EM CATEGORIA 6.
ELETRODUTO ABAIXO DO PISO ELEVADO ('ENTREPISOS').
CONJUNTO DE 2 TOMADAS RJ-45 CAT.6 INSTALADAS EM CAIXA 4X4" EM
CANALETAS NAS MESAS.
CANALETAS DE 3 SEPTOS INSTALADAS NAS MESAS PARA PASSAGEM
DOS CABOS DE ELÉTRICA ESTABILIZADA, TELECOM. E SONORIZAÇÃO.
04xUTP4P
01-04
INDICAÇÃO DE QUANTIDADE DE CABOS UTPS PASSANDO EM
ELETRODUTO E INDENTIFICAÇÃO DO NÚMERO DOS PONTOS.
U1
U2
U3
U4
U5
U6
RÉGUA DE (08) OITO TOMADAS
2P+T/15A (NO FUNDO DO RACK)
SWITCH1-01- 24 PORTAS
GUIA FRONTAL PARA CABOS
CX. SOM
01
HDMI
QDCEC1-02
QDCEE-01
ELETROCALHA EXISTENTE
0404
PROJETO ELÉTRICO
ENGENHARIA E PROJETOS
RESPONSÁVEL
CONTRATANTE
Tribunal de Justiça Militardo Estado de Minas Gerais
CAIXA DE LIGAÇÃO PARA ELETRODUTO (CONDULETE)
ELETRODUTO NO ENTREFORRO.
CAIXAS DE SOM.
1 - ELETRODUTOS NÃO ESPECIFICADOS A SEREM INSTALADOS DEVERÃO SER DE AÇO
GALVANIZADO Ø3/4", AS CONEXÕES (CURVAS E LUVAS) DEVERÃO TER AS MESMAS
CARACTERÍSTICAS;
2 - DEVERÃO SER INSTALADAS BUCHAS E ARRUELAS DE ACABAMENTO EM TODAS AS
EXTREMIDADES DOS ELETRODUTOS.
3 - TODOS OS CABOS DEVERÃO SER IDENTIFICADOS COM ANILHAS NO INICIO E FINAL, NAS
CAIXAS DE PASSAGEM E PONTOS DE SAÍDA.
4 - OS CABOS INSTALADOS NO 'ENTREPISOS' SERÃO ORGANIZADOS ATRAVÉS DE ESPIRAL
ORGANIZADORA DE CABOS.
5 - OS EQUIPAMENTOS DE SONORIZAÇÃO SÃO EXISTENTES.
6 - A ESPECIFICAÇÕES DOS COMPONENTES PODE SER ALTERADA PARA ADEQUAÇÃO AOS
EQUIPAMENTOS.
ELETRODUTO ABAIXO DO PISO ELEVADO ('ENTREPISOS').
PONTOS DE MICROFONE
CANALETAS DE 3 SEPTOS INSTALADAS NAS MESAS PARA PASSAGEM
DOS CABOS DE ELÉTRICA ESTABILIZADA, TELECOM. E SONORIZAÇÃO.
INDICAÇÃO DE QUANTIDADE DE CABOS PORALIZADOS EM
ELETRODUTO E INDENTIFICAÇÃO DAS CAIXAS.
CX. SOM
02
MI-01
MI-02
MI-03MI-04MI-05
MI-06
MI-07
MI-08MI-09