Upload
mrfe
View
218
Download
0
Embed Size (px)
Citation preview
8/13/2019 O nosso.pdf
1/8
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 12, NO. 2, MARCH 1997 311
Three-Phase Four-Wire ShuntActive Filter Control Strategies
Maurcio Aredes, Student Member, IEEE Jurgen Hafner, and Klemens Heumann, Member, IEEE
AbstractThis paper describes a three-phase four-wire shuntactive power filter using a conventional three-leg converter,without the need of power supply at dc bus. Two approacheshave been developed to control the active filter. Both controlstrategies consider harmonics and zero sequence components inthe voltage and current simultaneously. The first one providesconstant power and the second one sinusoidal current to thesource, even under unbalanced voltage conditions. Simulationresults from a complete model of shunt active filter are presentedto validate and compare the control strategies.
Index TermsActive power filters, active power line condition-ers, FACTS, instantaneous active and reactive power.
I. INTRODUCTION
ACTIVE power filters for three-phase systems withoutneutral conductor have been successfully developed, andnowadays some commercial products are already available.
Although three-phase four-wire active filters have been intro-
duced in the 1980s [1], the development is still in its infancy
and no experimental prototype has been put in operation
outside the universities.
Some researches appoint the four-leg converter topology as
the best alternative to implement a three-phase four-wire active
power filter [2][4]. Alternatively, the authors present here an
interesting solution that uses a conventional three-leg converter
to implement a three-phase four-wire shunt active filter.
The instantaneous power theory ( theory) has been used
successfully to control active power filters for three-phase
systems [5][7]. This theory was extended in [8] and [9] for
applications in three-phase four-wire systems. Here, a critical
comparison between two control strategies that provide load
current compensation including zero sequence components and
considering distorted system voltage is carried out.
The first one, the constant source instantaneous power
strategy, was introduced in [9]. It compensates the current of
a nonlinear load such that the compensated current shall draw
a constant active power from the network, even if the system
voltage is already distorted. However, its dynamics within acomplete simulation model of shunt active filter has not been
reported so far and there are some difficult aspects that should
be evidenced.
The second approach is the sinusoidal source current strat-
egy. It compensates currents of a nonlinear load to provide
Manuscript received January 26, 1995; revised September 6, 1996.M. Aredes is with Cepel-Centro de Pesquisas de Energia Eletrica.J. Hafner and K. Heumann are with Technische Universitat Berlin, Institut
fur Allgemeine ElektrotechnikSekr. E2, 10587 Berlin, Germany.Publisher Item Identifier S 0885-8993(97)01851-6.
sinusoidal, balanced currents to the source, even when the
system voltage is distorted and/or unbalanced.
The performance of both control strategies will be compared
and discussed in details through simulation results from a
complete model of shunt active filter including the three-
leg converter and its pulse width modulation (PWM) current
control.
II. PWM CONVERTERS FOR
THREE-PHASE FOUR-WIRE SYSTEMS
In this section, two configurations of Voltage Source Invert-
ers (VSI), which can be used in three-phase four-wire systems,will be presented. The fundamental difference between the VSI
of Fig. 1(a) and (b) is the number of power semiconductor
devices. A conventional three-leg converter is used in Fig. 1(a)
and the ac neutral wire is connected directly to the midpoint ofthe dc bus, while in Fig. 1(b) the ac neutral is provided through
a fourth leg. Since the configurations have PWM current
control, they behave as controlled current source. The ac
currents generated by the VSI have some high-order harmonics
at the switching frequency, which can be easily filtered using
a small passive filter ( and in Fig. 1). Ideally, the currents
track accurately their references .
The controllability of the four switch-leg inverter topol-
ogy [Fig. 1(b)] is better than the split-capacitor inverter
topology [Fig. 1(a)] [2], [3]. However, the conventional three-
leg converter is preferred because of its lower number of power
semiconductor devices [10], [11]. The problems related to the
dc capacitor voltage control by using the topology of Fig. 1(a)
will be discussed below and a simple control circuit will be
proposed later.
Fig. 2 shows a typical motion of the -phase VSI current
controlled by a hysteresis-based PWM current controller. If the
current references are assumed to be composed from zero
sequence component, the line currents will
return through the ac neutral wire. This forces, in the split-
capacitor inverter topology, the current of each phase to floweither through or through and to return through the ac
neutral wire. The currents can flow in both directions through
the switches and capacitors. Table I summarizes the conditions
that cause voltage variations in the capacitors and
for a zero sequence current reference in the split-capacitor
inverter topology.
When rises and decreases, but not with
equal ratio because the positive and negative values of
are different and depend on the instantaneous values of the ac
phase voltages. The inverse occurs when . The dc
08858993/97$10.00 1997 IEEE
8/13/2019 O nosso.pdf
2/8
312 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 12, NO. 2, MARCH 1997
(a)
(b)
Fig. 1. Three-phase four-wire PWM converters: (a) three-leg converter(split-capacitor inverter topology) and (b) four-leg converter (fourswitch-leg inverter topology).
Fig. 2. Hysteresis-band PWM current control.
TABLE IVARIATION CONDITIONS FOR THE C APACITOR VOLTAGES
AND
voltage variation depends also on the shape of the current
reference and the hysteresis bandwidth. Therefore, the total dc
Fig. 3. Three-phase four-wire shunt active power filter using a conventionalthree-leg converter.
voltage, as well as the voltage difference ( ) will
oscillate not only at the switching frequency, but also at thecorresponding frequency of that is being generated by the
VSI.
In the example given in Fig. 2, the phase current causes
voltage variations such that at the end of the period the voltage
is higher and lower. If a dynamic offset level is
added to both limits of the hysteresis-band, it is possible to
control the capacitor voltagedifferenceand to keep it within an
acceptable tolerance margin. For instance, a negative offset in
Fig. 2 counteracts the above voltage variation. Later, a simple
control scheme will be proposed to do it.
III. SHUNTTHREE-PHASE FOUR-WIRE ACTIVE FILTER
The shunt three-phase four-wire active power filter con-
figuration that will be explored in this paper is presented
in Fig. 3. It is composed from a conventional three-leg VSI
with a dynamic hysteresis-band PWM current control and an
active filter controller that realizes an instantaneous control
algorithm. The inputs of this controller are the instantaneous
phase voltages and line currents of the load. Its outputs are
the instantaneous three-phase current references and
. The voltage regulator supervises the dc capacitor voltages
and provides two control signals, and , as shown in
Fig. 3. The signal compensates for losses in the PWM
converter, which tends to discharge the dc capacitors and
. The signal is the dynamic offset level used to controlthe capacitor voltage difference, as will be seen later.
IV. SHUNT ACTIVE FILTER CONTROL
To control the active filter, two approaches are consid-
ered: 1) the constant source instantaneous power strategy
that provides constant real power to the source, even under
unbalanced voltage source, and 2) the sinusoidal source cur-
rents strategy that provides sinusoidal currents to the source,
even under unbalanced voltage source. In both strategies the
whole zero-sequence current of the load is compensated, but
it is impossible to satisfy simultaneously both conditions:
8/13/2019 O nosso.pdf
3/8
AREDES et al.: THREE-PHASE FOUR-WIRE SHUNT ACTIVE FILTER CONTROL STRATEGIES 313
sinusoidal currents and constant power at the source if the
system voltage is unbalanced and/or distorted.
A. Constant Source Instantaneous Power Strategy
The physical meaning of the instantaneous active and re-
active power ( - theory) will be briefly summarized below
for better understanding the optimal load flow conditions that
guides the realization of this control strategy.The active filter controller of Fig. 3 uses the - - transfor-
mation and the instantaneous power defined in this reference
frame [5][7]. The instantaneous voltages and currents of a
nonlinear load are transformed into the - - axis by
(1)
(2)
where and are phase voltages and and are
line currents.
The real power , the imaginary power and the zero
sequence power are defined as
(3)
The physical meaning of these instantaneous powers is
detailed in [8] and [9], and Fig. 4 summarizes those concepts.Three points should be remarked.
The total instantaneous energy flow per time unit, that
is, the instantaneous active three-phase power is always
equal to the sum of the real power and the zero-sequence
power.
The zero-sequence components of voltages and currents
do not contribute to the instantaneous powers and .
The imaginary power represents an energy that can
be constant or not and is being exchanged between
the phases of the system. This means that does not
contribute to the energy transfer between source and loadat any time.
An optimal power flow can be provided to the source,
even under unbalanced and nonsinusoidal voltage conditions.
This occurs when the active filter compensates the powers
(alternating part of the real power), and of
the load. Fig. 5 shows the optimal power flow in terms of
- - coordinates. It shows that the source supplies only the
averagereal power to the load and the averagereal power
to the active filter. The additional power is equal to the
sum of , to cover the converter losses and , to provide
energy balance inside the active filter. If an active filter is
Fig. 4. Physical meaning of the instantaneous powers defined in the - - reference frame.
Fig. 5. Optimal power flow related to the - - reference frame.
used for compensating , it has to compensatefullythe power
, because it is impossible to produce separately
from [9]. The zero sequence power that the active filter
supplies to the load can be taken as a balanced real power
from the source, since it is always possible to generate
with , even under nonsinusoidal conditions.
The entire control block diagram of the three-phase four-
wire shunt active filter is presented in Fig. 6. The control
circuit as shown in this figure realizes the constant source
instantaneous power strategy. There are two shaded areasinvolving the 800-Hz cutoff frequency low-pass filters and the
low-pass filter for the power . These areas will be changed
in the next section to adapt the circuit to the sinusoidal source
current strategy.
Unfortunately, the phase voltages could not be used directly
in the control because of instability problems. It was verified
that resonance between the source impedance and the small
passive filter ( and in Fig. 3) can appear. Therefore, low-
pass filters were used with a relatively high cutoff frequency
(800 Hz) to attenuate voltage harmonics at the resonance
frequency, which is higher than 800 Hz. These filters turn
8/13/2019 O nosso.pdf
4/8
314 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 12, NO. 2, MARCH 1997
Fig. 6. Control block diagram of the shunt active filter.
the system stable, but also degenerate the compensation char-
acteristics of the shunt active filter, as will be shown later.
The - - transformation box of Fig. 6 realizes (1)(3).
Two filters with 50-Hz cutoff frequency separate the powers
and from and , respectively. These signals are used
in the - current reference box, which realizes the following
equations:
(4)
where
(5)
Finally, the - - inverse transformation box calculates the
instantaneous current references to the PWM current control
as
(6)
With this approach the active filter supplies the whole of
the load. If zero sequence voltage is not present in the system,
the zero sequence power is always zero. In this case, the
zero sequence current of the load is compensated without
the need of energy balance inside the active filter ( ).
The signal is used in (5) as anaverage real powerand
is obtained from the voltage regulator, as shown in Fig. 6. The
sum of and is compared to a dc bus voltage reference
( ) and the deviation is filtered and multiplied by , to
match the desired amplitude for the ac current component
that neutralizes the dc bus voltage variations. Low-pass filters
with a cutoff frequency at 20 Hz are inserted in the voltage
regulator to render it insensitive to the fundamental frequency
(50-Hz) voltage variations, which appear when the active filter
compensates the fundamental zero sequence current of the
load, even when , as explained in Fig. 2. Note that
the compensation of and of the load also causes voltage
variation (see Fig. 5). Further, this slower feedback loop is also
useful to correct voltage variations due to compensation errors
that occur during transient response of the shunt active filter.
Due to the same reasons above, another low-pass filter is
applied in the circuit that generates the signal . In this case,the filtered voltage difference produces
according to the following limit function:
(7)
where is the dc bus voltage reference. The signal
actuates as a dynamic offset level that is added to both
hysteresis-band limits in the PWM current control, as shown
in Fig. 6, which is
upper hysteresis band limit
lower hysteresis band limit(8)
where is the instantaneous current reference
given by (6) and is a fixed semi-bandwidth of the hysteresis
control. Thus, the signal shifts the hysteresis-band to change
the switching times such that
rises and lowers
rises and lowers(9)
8/13/2019 O nosso.pdf
5/8
AREDES et al.: THREE-PHASE FOUR-WIRE SHUNT ACTIVE FILTER CONTROL STRATEGIES 315
Fig. 7. Block diagram of the fundamental positive-sequence voltage detector.
B. Sinusoidal Source Current Strategy
The active filter can compensate load currents under unbal-
anced system voltages to provide sinusoidal, balanced currents
to the source but now, disregarding the optimal power flow
proposed in Fig. 5. For this purpose, a positive sequencedetector must replace the 800-Hz cutoff frequency low-pass
filters (shaded area in Fig. 6). The phase angle and frequency
of the fundamental positive sequence voltage component ( )
must be accurately determined by the detector, in order to
allow the active filter to compensate the fundamental reactive
power of the load. The active filter must produce ac currents
( ) orthogonal to the voltage component . Otherwise it
would also produce active power.
The positive sequence voltage detector as presented in Fig. 7
not only satisfies the above constraints, but also determines
correctly the amplitude from . First, an integrated circuit
with a VCO chip (PLL circuit) should determine accurately
the fundamental frequency ( ) of the system voltage,which may be unbalanced and contain harmonics. Afterwards,
the fundamental frequency is used as input to a sine-wave
generator that produces three auxiliary signals ( ) to
be used as fundamental positive sequence currents along
the detector of Fig. 7. The phase angle and the amplitude of
these sine signals are not important,except that they must keep
120 among themselves and have equal amplitudes.
Again, the voltage detector uses an algorithm based on the
instantaneous powers defined in the - - reference frame.
However, the average values of the real ( ) and imaginary
( ) powers are considered here. The average powers
and are composed only from the fundamental positive
sequence voltage , since the auxiliary currentsare also composed only from a fundamental positive sequence
component. In this case, the influence of the fundamental
negative sequence voltage and harmonics will appear in the
high-frequency components of and .
The - voltage reference box of Fig. 7 calculates
(10)
Finally, the - - instantaneous values ( ) of the
fundamental positive sequence voltage, are determined in
the - - inverse transformation box, without errors in the
amplitude or phase angle, as
(11)
If the voltages calculated in (11) are considered as input
to the main control circuit (Fig. 6), instead of the filtered
voltages used previously, now the compensating powers
and will include the fundamental negative sequence power,
the fundamental reactive power, and the harmonic power.
Thus, the active filter controller handles the load currents as
connected to a sinusoidal, balanced voltage source. In this
case, if , and are compensated by the shunt
active filter, the source currents become sinusoidal, balanced,
and composed only from the active portion of the fundamental
positive sequence current of the load that is in phase with .Therefore, the sinusoidal source current strategy is realizeddoing the following changes in Fig. 6:
1) to replace the 800-Hz low-pass filters of Fig. 6 with the
circuit of Fig. 7;
2) to remove the 50-Hz low-pass filter that obtains in
Fig. 6, because the new input voltages and
do not contain any zero-sequence voltage component
( ) and is always zero.
At this point, it should be remarked that the voltage regulator
of Fig. 3 now has an additional task besides those described
previously, that is, it should correct errors in power compen-
sation. This errors arise because the feedforward control in
the main circuit is now unable to supervise the zero sequencepower. Another kind of error will also appear. To understand
this point, a simple example follows.
Suppose that the system voltages and load currents are
composed only from fundamental positive and negative se-
quence components. As expected, the active filter will supply
the whole negative sequence current ( ) to the load. How-
ever, the ac voltage at the shunt active filter contains also
negative sequence component at same frequency. So if it is
not orthogonal to , the active filter will supply/absorb a
nonzero average negative-sequence power. Since the power
compensation error causes voltage variation at the dc bus,
8/13/2019 O nosso.pdf
6/8
316 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 12, NO. 2, MARCH 1997
TABLE IIMAIN PARAMETERS OF THE SIMULATED SYSTEM BASED ON FIG. 3
the slower feedback control loop of the voltage regulator willsense it and will change the signal to make the active
filter to absorb/supply a positive-sequence power from the ac
network to neutralize the above voltage variation. This occurs
because the active filter current references are calculated only
from [ of (11)].
V. SIMULATED RESULTS
A complete model of the shunt active filter was implemented
in a digital simulator and the most important results will be
presented to compare both control strategies. The fundamental
frequency of the system is 50 Hz. The source voltages are
composed from arbitrarily chosen phasors in terms of sym-metrical components. The rms amplitude and phase angle of
these phasors are
V
V
The other main system parameters based on Fig. 3 are sum-
marized in Table II.
Two simulations that use the same system parameters, but
realize different control strategy, will be shown. The phasevoltages at the load were almost the same for both simulation
cases and Fig. 8 shows the voltages for the constant sourceinstantaneous powercase. The load current was the same for
both simulations (Fig. 9). The diode bridge was connected
at ms and the controlled (thyristor) bridges were
connected after ms, according to their firing angles
(see Table II). Then, at ms, the firing pulses of the
three-phase thyristor bridge were blocked, as shown in Fig. 9.
The active filter was connected at ms. Fig. 10 shows
the filtered (no switching frequency) line currents of the active
filter for the sinusoidal source current case. For the constant
Fig. 8. System voltages.
Fig. 9. Load currents.
source instantaneous powercase, the current of the active
filter is presented in Fig. 11. These figures show that both
control strategies have the same dynamic behavior.
The compensated currents that flow through the source are
shown in Fig. 12(a) for the constant source instantaneouspowercase and in Fig. 12(b) for the sinusoidal source current
case. Although both approaches provide fast response and
equally compensate the neutral current of the load, they cannot
avoid the harmonic currents that are excited by the harmonic
voltages of the source and are flowing to the passive filter
( F ). Nevertheless, from a harmonic point
of view, the sinusoidal source current strategy offers a better
compensation for the source currents. Due to this reason, this
control strategy has been preferred and experimental results
from a laboratory prototype using this control strategy were
reported in [11].
8/13/2019 O nosso.pdf
7/8
AREDES et al.: THREE-PHASE FOUR-WIRE SHUNT ACTIVE FILTER CONTROL STRATEGIES 317
Fig. 10. Active filter currents when the sinusoidal source current strategyis applied.
Fig. 11. Active filter current when theconstant source instantaneous powerstrategy is applied.
(a)
(b)
Fig. 12. Currents of the power supply compensated by (a) the constantsource instantaneous power strategy and (b) the sinusoidal source currentstrategy.
Fig. 13 compares the three-phase instantaneous power (
) of the load with the powers from the compensated line
currents, for both control strategies. The constant source
instantaneous power strategy (pconst curve) should present a
perfectly smoothed instantaneous power at source side. Unfor-
tunately, it presented a poor performance due to the presence
Fig. 13. Three-phase instantaneous powers.
Fig. 14. Imaginary powers.
Fig. 15. Capacitor voltages at the dc bus.
of the 800-Hz cutoff frequency low-pass filters (Butterworth
Filter fifth order), applied in the measured system voltages to
solve problems of instability. For the level of voltage distortion
considered, the need of low-pass filter in the measured voltagesin case of using the constant source instantaneous power
strategycauses power compensation errors at the same order
of magnitude as the sinusoidal source current strategy. The
average switching frequency of the PWM inverter is about 13
kHz, and the losses in the snubber circuits are so high as the
average load power.
The imaginary powers illustrated in Fig. 14 were calculated
from the same voltages and currents used in Fig. 13. The
curve for the constant power strategy contains a small negative
average value because the 800-Hz cutoff frequency filters
delay the measured system voltages. This does not occur in the
sinusoidal source current strategy and confirms the efficiency
of the positive sequence voltage detector (Fig. 7).The dc capacitor voltage variations were almost similar in
both cases, as shown in Fig. 15. It is possible to see a 50-
Hz component that is caused by the zero-sequence current
compensation, as explained early. A discharge of the dc
capacitors occurred when the loads is connected. Contrarily,
an overvoltage occurred when the three-phase thyristor bridge
is disconnected.
VI. CONCLUSIONS
Two control schemes for a shunt three-phase four-wire
active power filter employing a conventional three-leg con-
8/13/2019 O nosso.pdf
8/8
318 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 12, NO. 2, MARCH 1997
verter were developed and a critical comparison between both
approaches was carried out. The three-leg converter topology
was preferred due to its lower number of power semiconductor
devices, and a dynamic hysteresis current control was devel-
oped to overcome the problems related with the dc voltage
difference between dc capacitors.
A three-phase active filter without neutral wire could be
realized using a two-leg converter if the split-capacitor
inverter topology and the dynamic hysteresis current controlare applied, or generally use ( )-leg converter in -wire
systems.
Although the constant source instantaneous power strategy
is easier to realize, all simulation results indicated that thesinu-
soidal source current strategy should be the best alternative to
control a shunt active power filter. Experimental results using
this control strategy were successfully obtained and already
reported in [11].
REFERENCES
[1] G. Dinykel and R. Gretsch, Kompensator fur oberschwingungen und
blindleistung,ETZ Archiv., vol. 9, no. 1, pp. 914, 1987.[2] C. A. Quinn and N. Mohan, Active filtering of harmonic currentsin three-phase, four-wire systems with three-phase and single-phasenonlinear loads, in APEC92Applied Power Elec. Conf., 1992, pp.829836.
[3] C. A. Quinn, N. Mohan, and H. Mehta, A four-wire, current-controlledconverter provides harmonic neutralization in three-phase, four-wiresystems, in APEC93Applied Power Elec. Conf., 1993, pp. 841846.
[4] D. Sutanto and M. Bou-Rabee, Active power filters with reactive powercompensation capability, in Int. Power Eng. Conf., Singapore, Mar.1993, pp. 7378.
[5] H. Akagi, Y. Kanazawa, and A. Nabae, Generalized theory of theinstantaneous reactive power in three-phase circuits, in IPEC83Int.Power Elec. Conf., Tokyo, Japan, 1983, pp. 13751386.
[6] H. Akagi, Y. Kanazawa, and A. Nabae, Instantaneous reactive powercompensator comprising switching devices without energy storage com-ponents, IEEE Trans. Ind. Appl., vol. IA-20, no. 3, pp. 625630,1984.
[7] H. Akagi, A. Nabae, and S. Atoh, Control strategy of active powerfilter using multiple voltage-source PWM converters, IEEE Trans. Ind.
Appl., vol. IA-22, no. 3, pp. 460465, 1986.[8] E. H. Watanabe, R. M. Stephan, and M. Aredes, New concepts of
instantaneous active and reactive powers in electrical systems withgeneric loads, IEEE Trans. Power Delivery, vol. 8, pp. 697703, Apr.1993.
[9] M. Aredes and E. H. Watanabe, New control algorithms for series andshunt three-phase four-wire active power filters, IEEE Trans. Power
Delivery, vol. 10, pp. 16491656, July 1995.[10] G. Superti-Furga, E. Tironi, and G. Ubezio, General purpose low-
voltage power conditioning equipment, in IPEC95Int. Power Elec.Conf., Yokohama, Japan, Apr. 1995, pp. 400405.
[11] M. Aredes, J. Hafner, and K. Heumann, A three-phase four-wire shuntactive filter using six IGBTs, in EPE95Eur. Conf. Power Elec.
Appl., Sevilla, Spain, Sept. 1995, vol. 1, pp. 1.8741.879.
Maurcio Aredes was born in Sao Paulo State,Brazil, on August 14, 1961. He received the B.Sc.degree from Fluminense Federal University, Rio deJaneiro State in 1984, the M.Sc. degree in electri-cal engineering from Federal University of Rio deJaneiro in 1991, and the Dr.-Ing. degree (honors)from Technische Universitat Berlin in 1996.
From 1985 to 1988, he worked as a Commission-ing and Project Engineer at the Itaipu HVDC Trans-mission System, and from 1988 to 1991 he workedas Management Engineer in the Itaipu Power Plant
SCADA Project. At present, he is working within CEPELCentro dePesquisas de Energia Eletrica, Rio de Janeiro, and his main research areaincludes HVDC systems, active power filters, and FACTS technology.
Jurgen Hafner was born in Grobottwar, Germany, on August 7, 1964.He received the diploma degree in electrical engineering in 1991 from theTechnical University, Berlin.
Currently, he is working as an Assistant at the Technical University, Berlin.His research area includes active power filters, control, and simulation.
Klemens R. Heumann was born in Lunen, Germany, on May 15, 1931.He received the Dipl.-Ing. degree from Rheinisch-Westfalische TechnischeHochschule, Aachen, Germany, in 1956, and the Dr.-Ing. degree from Tech-nische Universitat Berlin, in 1961.
He was a Research Engineer from 1956 to 1968 and a General Manager
from 1969 to 1978 in the AEG Research Institute, Berlin. He became aProfessor of Power Electronics at the Universitat Hannover in 1978, andin 1983 he joined the Technische Universitat Berlin, where he is presentlya Professor. He has worked as a Consultant in various industries and is theauthor of four books and author and co-author of more than 100 papers.
Dr. Heumann is the recipient of the 1985 IEEE Power Electronics SocietyWilliam E. Newell Award.