PAINEL MOTOR DRENAGEM CARGA INSTALADA ( VA) ILUMINAÇÃO 0 TOMADAS 0 APARELLHO AQUECIMENTO 0 APARELHO AR CONDICIONADO 0 MOTOR 2700 TOTAL 2700 CÁLCULO DA DEMANDA D(kVA) =a+b+c+e ILUMINAÇÃO E TOMADAS a = P*FD*FP P= 0 + 0 = 0 FD= 86 FP= 1 a= 0 VA MOTORES E = P*FD P= 2700 VA FD= 1 * FATOR DE DEMANDA CONFORME ANEXO G b= 2700 VA D(kVA) =a+b+c+e * FATOR DE DEMANDA CONFORME ANEXO D

PLANILHA DE CÁLCULO.xlsx

Embed Size (px)

Text of PLANILHA DE CÁLCULO.xlsx

PAINEL MOT DREPAINEL MOTOR DRENAGEM

CARGA INSTALADA ( VA)

ILUMINAO0TOMADAS0APARELLHO AQUECIMENTO0APARELHO AR CONDICIONADO0MOTOR2700TOTAL2700

CLCULO DA DEMANDA

D(kVA) =a+b+c+e

ILUMINAO E TOMADAS

a = P*FD*FP

P=0+0=0VAFD=86* FATOR DE DEMANDA CONFORME ANEXO D FP=1a=0VA

MOTORESE = P*FD

P=2700VAFD=1* FATOR DE DEMANDA CONFORME ANEXO Gb=2700VA

D(kVA) =a+b+c+e

D =2.70kVA* FATOR DE DEMANDA CONFORME ANEXO JD 10

DISJUNTOR DE PROTEO = 3X30ACABO = 6mm

DISJUNTOR DE PROTEO = 3X30ACABO= 6mm

PAINEL MOT POTPAINEL MOTOR AGUA POTAVEL

CARGA INSTALADA ( VA)

ILUMINAO0TOMADAS0APARELLHO AQUECIMENTO0APARELHO AR CONDICIONADO0MOTOR5400TOTAL5400

CLCULO DA DEMANDA

D(kVA) =a+b+c+e

ILUMINAO E TOMADAS

a = P*FD*FP

P=0+0=0VAFD=86* FATOR DE DEMANDA CONFORME ANEXO D FP=1a=0VA

MOTORESE = P*FD

P=5400VAFD=1* FATOR DE DEMANDA CONFORME ANEXO Gb=5400VA

D(kVA) =a+b+c+e

D =5.40kVA* FATOR DE DEMANDA CONFORME ANEXO JD 10

DISJUNTOR DE PROTEO = 3X30ACABO = 6mm

DISJUNTOR DE PROTEO = 3X30ACABO= 6mm

PAINEL MOT ELEVPAINEL MOTOR ELEVADOR

CARGA INSTALADA ( VA)

ILUMINAO0TOMADAS0APARELLHO AQUECIMENTO0APARELHO AR CONDICIONADO0MOTOR9200TOTAL9200

CLCULO DA DEMANDA

D(kVA) =a+b+c+e

ILUMINAO E TOMADAS

a = P*FD*FP

P=0+0=0VAFD=86* FATOR DE DEMANDA CONFORME ANEXO D FP=1a=0VA

MOTORESE = P*FD

P=9200VAFD=1* FATOR DE DEMANDA CONFORME ANEXO Gb=9200VA

D(kVA) =a+b+c+e

D =9.20kVA* FATOR DE DEMANDA CONFORME ANEXO JD 10

DISJUNTOR DE PROTEO = 3X30ACABO = 6mm

DISJUNTOR DE PROTEO = 3X30ACABO= 6mm

DEMANDA PRDIOENTRADA DO PRDIO

CLCULO DA DEMANDA

D(kVA) =Dpredio+D Servio

ILUMINAO E TOMADAS

D Predio = 1,2 * (a*b)

a =anexo U=9.64b =anexo T=1.76

Dservio= 22.6kVA

D(kVA) =Dpredio+D Servio

D(kVA) =42.96kVA

* FATOR DE DEMANDA CONFORME ANEXO JDISJUNTOR DE PROTEO = 3X125ACABO= 50mm

SERVIOSERVIO

CARGA INSTALADA ( VA)

ILUMINAO2380TOMADAS5300APARELLHO AQUECIMENTO0APARELHO AR CONDICIONADO0MOTOR20000TOTAL27680

CLCULO DA DEMANDA

D(kVA) =a+b+c+e

ILUMINAO E TOMADAS

a = P*FD*FP

P=2380+5300=7680VAFD=86* FATOR DE DEMANDA CONFORME ANEXO D FP=1a=6604.8VA

MOTORESE = P*FD

P=20000VAFD=80* FATOR DE DEMANDA CONFORME ANEXO Gb=16000VA

D(kVA) =a+b+c+e

D =22.60kVA* FATOR DE DEMANDA CONFORME ANEXO JDISJUNTOR DE PROTEO = 3X70ACABO= 25mm

201_301_401 (2)AP's. 201 / 301 / 401REA= 54,76 m

CARGA INSTALADA ( VA)

ILUMINAO900TOMADAS8900APARELLHO AQUECIMENTO15200APARELHO AR CONDICIONADO2200MOTOR0TOTAL27200

CLCULO DA DEMANDA

D(kVA) =a+b+c+e

ILUMINAO E TOMADAS

a = P.FD.FP

P=900+8900=9800VAFD=37%* FATOR DE DEMANDA CONFORME ANEXO D FP=1a=3626VA

APARELHOS AQUECIMENTO03 APARELHOS

b = P.FD.FP

P=15200VAFD=70%* FATOR DE DEMANDA CONFORME ANEXO IFP=1b=10640VAAPARELHOS AR CONDICIONADO02 APARELHOSc = P.FD

P=2200VAFD=1* FATOR DE DEMANDA CONFORME ANEXO EFP=1b=2200VAD(kVA) =a+b+c+e

D =16.47kVA* FATOR DE DEMANDA CONFORME ANEXO JDISJUNTOR DE PROTEO = 3X50ACABO= 10mm

202_302_402 (2)AP's. 202 / 302/ 402REA= 37,84 m

CARGA INSTALADA ( VA)

ILUMINAO900TOMADAS5200APARELLHO AQUECIMENTO8400APARELHO AR CONDICIONADO2200MOTOR0TOTAL16700

CLCULO DA DEMANDA

D(kVA) =a+b+c+e

ILUMINAO E TOMADAS

a = P+FD+FP

P=900+5200=6100VAFD=47%* FATOR DE DEMANDA CONFORME ANEXO D FP=1a=2867VA

APARELHOS AQUECIMENTO02 APARELHOS

b = P.FD.FP

P=8400VAFD=75%* FATOR DE DEMANDA CONFORME ANEXO IFP=1b=6300VAAPARELHOS AR CONDICIONADO02 APARELHOSc = P.FD

P=2200VAFD=1* FATOR DE DEMANDA CONFORME ANEXO EFP=1b=2200VAD(kVA) =a+b+c+e

D =11.37kVA* FATOR DE DEMANDA CONFORME ANEXO JDISJUNTOR DE PROTEO = 3X40ACABO= 10mm

203_303_403AP's. 203 / 303/ 403REA= 52,74 m

CARGA INSTALADA ( VA)

ILUMINAO860TOMADAS6600APARELLHO AQUECIMENTO8400APARELHO AR CONDICIONADO2200MOTOR0TOTAL18060

CLCULO DA DEMANDA

D(kVA) =a+b+c+e

ILUMINAO E TOMADAS

a = P.FD.FP

P=860+6600=7460VAFD=43%* FATOR DE DEMANDA CONFORME ANEXO D FP=1a=3207.8VA

APARELHOS AQUECIMENTO02 APARELHOS

b = P.FD.FP

P=8400VAFD=75%* FATOR DE DEMANDA CONFORME ANEXO IFP=1b=6300VAAPARELHOS AR CONDICIONADO02 APARELHOSc = P.FD

P=2200VAFD=1* FATOR DE DEMANDA CONFORME ANEXO EFP=1b=2200VAD(kVA) =a+b+c+e

D =11.71kVA* FATOR DE DEMANDA CONFORME ANEXO JDISJUNTOR DE PROTEO = 3X40ACABO= 10mm

Plan1MEMORIAL DE CLCULO

OBJETO:PROJETO DE PAINEL DE MEDIO, RAMAL DE ENTRADA E ELTRICA PREDIAL