    Metal-enclosed single busbar, Solid and Air-Insulated switchgearIEC Medium Voltage Switchgear up to 24 kV

    Xiria EExtendable switchgear for distribution substationsand commercial / industrial applications

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    2/20

    Hydraulics

    Powering

    business

    worldwide

    Next generation

    transportation

    Eaton is driving the

    development of new

    technologies from hybrid

    drivetrains and emission control

    systems to advanced engine

    components that reduce fuel

    consumption and emissions in

    trucks and cars.

    Higher expectations

    We continue to expand ouraerospace solutions and

    services to meet the needs of

    new aviation platforms,

    including the high-flying light jet

    and very light jet markets.

    Building on our strengths

    Our hydraulics business

    combines localised service and

    support with an innovative

    portfolio of fluid power

    solutions to answer the needs

    of global infrastructure projects,

    including locks, canals anddams.

    Powering Greener Buildings

    and Businesses

    Eatons Electrical Group is a

    leading provider of power

    quality, distribution and control

    solutions that increase energy

    efficiency and improve power

    quality, safety and reliability.

    Our solutions offer a growing

    portfolio of green products

    and services, such as energy

    audits and real-time energy

    consumption monitoring.

    Eatons Uninterruptible Power

    Supplies (UPS), variable-speed

    drives and lighting controls help

    conserve energy and increase

    efficiency.

    Eaton delivers the power inside hundreds of products that

    are answering the demands of todays fast changing world.

    We help our customers worldwide manage the power

    they need for buildings, aircraft, trucks, cars, machinery

    and entire businesses. And we do it in a way that

    consumes fewer resources.

    Automotive

    Aerospace

    Electrical

    Truck

    Hydraulics

    Automotive

    Aerospace

    Electrical

    Truck

    Hydraulics

    2

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    3/20

    MV Switchgear Technology

    is in our DNA

    Complete MV switchgear solutions

    The series of Eaton Medium Voltage systems offers switchgearand components for applications in distribution networks (mainstations, substations and transformer stations) and industrialpower supplies. These technically high quality systems are air- orepoxy-resin insulated and are always equipped with circuit-breakers based on proprietary vacuum interrupters.

    The medium voltage switchgear systems carrying Eatons brandare based on the use of vacuum circuit-breakers combined withsolid insulation material. This is an environmentally-friendlytechnology in comparison with the methods used by many othersuppliers, which use SF6 as an insulation medium.

    Eaton thus has a wide range of switching systems andcomponents that offer an environmentally friendly solution forevery application. Additionally, Eatons global service network

    provides maximum customer support in all regions of the world.

    Industry leading vacuum and solid insulation technology

    Through more than eighty years of innovation and experience,Eaton has developed environmentally friendly vacuum interrupterscapable of reliably switching both normal load currents and highstress fault currents.

    Eaton is one of the few companies in the world producing vacuuminterrupters and has succeeded in developing world class productswith international patents. This has been achieved throughcompany acquisitions over the years of Westinghouse, Cutler-Hammer, MEM and Holec.

    To increase the dielectric strength of the vacuum interrupter,Eaton has also designed vacuum interrupters that are encapsulatedin epoxy resin material. The medium voltage IEC circuit breakerfamily utilizes this solid insulation technology that has beencatering to a wide range of applications for more than 40 years.

    Eatons range ofSF6 free switchgearfor Medium Voltage

    3

    Eatons knowledge and understanding of industries,

    applications, technology and products enables us to offer

    customers safe, reliable and high performance solutions.

    We have been part of the Medium Voltage switchgear

    technology creation and therefore carry whats needed

    with us always!

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    4/20

    Xiria The Product FamilyXiria is the name of Eaton's product family for a new generation of medium voltage

    switchgear. The Xiria family started more than a decade ago with the introduction of

    the Xiria ring main unit.

    This ring main unit consists of a block containing three panels. Due to the quick acceptance and

    worldwide interest in more configurations, Eaton consequently developed a four, five and two panelblock. Due to the fact that the individual units cannot be coupled and are limited in the number ofpanels and protection and control equipment, the single panel version was developed. This singlepanel version is called Xiria E. E in this case stands for Extendable.

    The Xiria family includes multiple possibilities and configurations for Power consumption metering.These configurations are indicated as Xiria M-versions. M stands for metering. The transformers forpower consumption metering can be either integrated into the block-type Xiria switchgear or housedin a separate metering panel. This dedicated metering panel can be integrated with both the currentblock type switchgear and the new single extendable panels.

    By adding the Xiria E panel tothe current range of Xiria acomplete family, based on thesame and proven key techno-logies, is created. The Xiriablock type system is alreadyfrequently used for transformersstations, small industries,

    heavy duty applications andcommercial buildings. Withthe new Xiria E panel it is alsopossible to use the system inapplications with higherspecifications and a biggernumber of panels.

    Some applications are: Distribution substations

    for utilities Wind power plants Bigger industrial applications Hotels Shopping centres

    Office buildings Infrastructure projects

    (tunnels, subways, airports) Universities Hospitals Data centers

    4

    The complete solution

    Xiria(Block type)

    Xiria M(Metering)

    Xiria E(Extendable)

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    5/20

    Xiria EModular Switchgear for Smart Grid Applications

    Xiria E is the name of Eaton's new medium voltage

    switchgear for smart grid applications. The system ischaracterised by its high level of operational safety and

    suitable for applications up to 24 kV.

    The Xiria E switchgear isdesigned around Eaton'sproven vacuum interrupters,which require no maintenanceand are certified for 30,000operation cycles.

    All live parts in the availablepanels are single poleinsulated. The used materialsare shaped specifically toprovide optimum insulation

    combined with excellentthermal characteristics. Inaddition, the insulation isconfigured to provide effectivecontrol over electric fieldsaround the used components,thereby minimizing any risk ofinternal arcing.

    Within the Xiria E panels boththe primary parts and themechanisms are housed in afully enclosed housing whichprotects the whole systemagainst environmentalinfluences.

    The use of vacuum interruptersand solid insulation means thatthe Xiria E is environmentallyfriendly. These technologiesensure that this system is aconservational alternative toswitchgear systems usingSulfur Hexafluoride (SF6) gasfor insulation. The cost ofownership is also significantly

    reduced, as no regular testingof gas pressure or other routinemaintenance is needed andthere is no high end-of-life costassociated with ultimatelydisposing of the equipment.

    With panel dimensions of only500 mm width and a provisionfor cable connection from thefront, the Xiria E system iseconomical in its use of

    valuable floor space, and easyto accommodate in even themost restricted environments.For locations where there is nopossibility to exhaust aninternal arc into cellar, thesystem has the possibility toexhaust into the room. This isrealized by means of a specialchimney at the back side withintegrated arc absorbers.

    When it comes to the safety ofthe operating personnel theXiria E design leaves nothing tochance. All parts are fully

    enclosed by an internal arctested safe metal housing.Besides that the panels in thesystem are provided with directvisible indication of theintegrated earthing andON/OFF-position by means ofinspection windows in thefront.

    5

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    6/20

    Safe in Use

    Visible isolation by meansof inspection windows inthe front

    Compartments protectedagainst penetration ofobjects

    Capacitive voltage detectionsystem for verification ofsafe isolation from supply

    Logical mechanical andelectrical interlocks preventformal operation

    Smooth contemporarydesign

    Environmental Friendly

    Minimized number ofcomponents

    Environmental-friendlydesign with respect to thematerials used

    No use of SF6-gas forswitching and insulation

    Energy efficient productionand assembly with

    environmental energysources

    Minimal number oftransition points in primarydesign enable low energyloss during operation

    Only Re-usable and / orrecyclable materials used

    Reliable and Safe inOperation

    Complete design certifiedin accordance with IECstandards

    Arc fault tested accordingIEC 62271-200

    Quality assurance inaccordance withDIN EN 9001

    Routine tested

    Single pole insulatedprimary parts within onecompartment

    Primary parts and

    mechanism in sealed forlife fully enclosed housing

    Protected voltagetransformers

    Low Total Cost of Ownership

    Low initial costs due to: Panels with only 500 mm

    width

    Cable connection from thefront / wall standingarrangement

    No need for external arcchannel

    12 kV and 24 kV panels insame housing

    No costs during service due to:

    Robust design with

    minimum number of parts(routine tested in factory)

    Long-life solid insulatedcomponents as insulationmedium

    Maintenance free vacuumcircuit-breaker and load-break switch

    Primary parts andmechanism installed in afully sealed for life enclosedhousing

    No SF6 pressure checks

    Low end of life disposal costdue to:

    Vacuum switchingtechnology

    Solid insulation with air asisolating medium

    Recycling or re-use ofmaterials

    User Friendly

    Cable connection and user

    interfaces for operation onthe same front side of thepanel

    Ergonomic cable connectionheight

    Cable (secondary) entrypoints on both sides of thelow voltage compartmenttop plate

    Secondary cable terminalspositioned on a goodreachable place in the lowvoltage compartment

    Clear and simple straight-

    forward operation panels

    Features and Benefits(quick overview)

    6

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    7/20

    Circuit-breaker panel (example)

    7

    6. Inspection window

    7. Mechanism

    8. Cable cones

    9. Cable clamps

    10. Earth bar

    11. Busbar

    12. Change-over switch

    13. Vacuum interrupter

    14. Current transformers

    15. Voltage transformers

    16. Coil and resistor forprotection againstferroresonance

    1. Low Voltage compartment

    2. Protection relay

    3. Control panel with operationof the circuit-breaker andchange-over switch

    4. Mimic diagram

    5. Voltage detection system

    In addition, the number of panels capable of being used inan installation is unlimited as several sections can easily beconnected. As the panels can be quickly assembled andconnected, flexible commissioning of the switchgear is possible.The panels in the Xiria E system are compact (500 mm wide),resulting in considerable savings in costs and installation space.

    Basic Design

    The Xiria E system is

    modular in construction.

    This ensures that any

    panel combination and

    sequence is possible.

    13

    15

    1

    2

    5

    6

    8

    7

    16

    4

    3

    12

    10

    14

    9

    11

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    8/20

    8

    The vacuum circuit-breaker uses a simple and reliable springcharging mechanism for operation of the vacuum interrupters.The mechanism contains a low number of moving parts andmakes no use of lubricants. It is completely housed in a sealed

    for life enclosure and therefore needs no maintenance.

    Features

    With environmental friendly vacuum interrupters

    Simple spring charging mechanism

    No use of lubricants

    Housed in a sealed for life enclosure

    Manual or motor-operated

    Position indication by means of inspection windows andmechanical indicators

    Auxiliary contacts for Open/Closed position

    Main Components

    Vacuum circuit-breaker

    All panels are equipped with a change-over switch positionedin the same sealed for life enclosure as the circuit-breaker.The change-over switch consists of three shafts connected tothe busbars or earthing points. Since it is mechanically interlockedthe change-over switch can only be operated when the circuitbreaker is in the open position.

    Features

    Manual-operated switch with 2 positions (service / earthed)

    Maintenance free

    Housed in sealed for life enclosure

    Auxiliary contacts for service / earthed positions

    Position indication by means of inspection windows andmechanical indicators

    Mechanically interlocked with the vacuum circuit-breaker

    2-position change-over switch

    The busbars in the panel are housed in the same sealed for lifeenclosure as the circuit-breaker and change-over switch. To preventa possible internal arc all busbars are single phase insulated.

    Features

    Single phase insulated

    Air insulated

    Housed in a sealed for life enclosure

    Simple and robust construction Easy to couple

    Busbars

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    9/20

    9

    Polycarbonate and Thermo-plastic elastomer (TPE) is usedas high-quality primary insulationmaterials around live parts.

    By applying Polycarbonate andTPE for solid insulation ourdesign engineers can shape theparts specifically for optimalinsulation, robust construction

    and cooling purposes. In themany years of experience withdesign and manufacturing ofinsulation materials, we learned

    to construct smart single phaseinsulated constructions. Xiriautilizes optimal field controlthrough the special design ofall primary components.

    Eaton Core Technologies

    Solid insulation

    With conventional shapes forprimary components likebusbars and conductors, theelectrical field between thephases and between phase andearth is non-uniformlydistributed. In areas with highfield, partial break-through can

    initiate avalanches resulting inflash-overs. In-depth knowledgeabout breakthrough phenomenaand field steering techniquesenable us to prevent flash overcompletely. The result is aparticular compact design.

    Electrical field control

    Eaton vacuum interruptersconsist of a ceramic cylinder,housing a fixed and movablecontact. Movement of thecontact under vacuum

    conditions is facilitated by abellow. A shield surroundingthe contacts prevents theinsulators from becomingcontaminated by metal vapourproduced during currentinterruption. This shield alsoensures good potentialdistribution over the insulator.

    A typical feature of Eatonvacuum interrupters is thatthey are characterised by verylow arc voltage and short arctimes, resulting in very low arc

    energy. Contacts wear in avacuum interrupter is thereforevirtually negligible. Vacuuminterrupters are maintenancefree and are certified up to30,000 operation cycles.

    Vacuum technology: safe, compact and reliable

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    10/20

    Eaton's proven technologies

    have been integrated in the

    design and development of

    the Xiria in order to ensure

    that the switchgear is safe

    and has high operational

    reliability throughout its

    complete lifetime.

    Experience and knowledgegained over many years in theareas of cast resin technology,vacuum technology andelectrical field control havebeen implemented.

    The system has been

    thoroughly arc fault testedaccording to the latest standardIEC 62271-200.

    Within the Xiria design there are different technologies used to prevent an open arc.

    Single pole insulated primaryparts

    All high voltage parts are singlepole insulated. The insulationmaterials used for this arePolycarbonate and Thermo-plastic elastomer (TPE), bothhigh-quality materials withoptimal insulation characteristicresulting in minimiseddimensions.

    Protected Voltagetransformers

    Ferro resonance can cause thatvoltage transformers aredamaged and consequentlyinitiate an internal arc in theswitchgear. Our designprevents that the voltagetransformers are affected byferroresonance. A resistor anda saturable coil are installed inthe tertiary circuit of thevoltage transformer.

    Use of Electrical Field control

    Engineers designed the wholeconstruction of primary parts,housed in the sealed for lifetank, based on Eaton's keytechnology for electrical fieldcontrol. By means of specialshapes and dimensions thepossibility of an open arc isminimized.

    Reliable and Safe in Operation

    Preventing an internal arc

    10

    Sealed for life fully enclosedhousing

    Both the primary parts of theunit and the mechanisms arehoused in a fully enclosed(sealed for life) housing whichprotects the whole system

    against environmentalinfluences and therefore makesit maintenance free. Thiscompartment can be classifiedas non-accessible and has anIP degree of IP55.

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    11/20

    Routine tests

    Various prescribed routinetests are carried out duringthe production of the switch-gear. To assure quality, allprocesses are in accordancewith DIN EN 9001. This means

    that at every stage ofproduction the components,circuit-breakers and currenttransformers are inspected forcorrect functioning. When theentire installation has been

    assembled, a thorough visualinspection is carried out,together with mechanical,functional and electrical checks.

    Philosophy on Internal arcs

    Eaton always puts extra focus

    on creating safe switchgear foroperators at all times. One ofthe biggest potential threats tooperators is an internal arc inswitchgear.

    Engineers therefore did every-thing necessary in design andconstruction to prevent internalarcs, despite the fact that it isvery rare for an operator to be infront (without operating) of theswitchgear at exactly the sametime that an internal fault

    occurs.

    Eaton supports the philosophythat it is best to avoid internalarcs than to cure, in line withthe relevant standard

    IEC 62271-200. Within the Xiriadesign a double preventionphilosophy is used. Firstly, thedesign is constructed in such away that an internal arc isprevented. In the unlikely casethat an internal arc could occur,the Xiria is equipped to provide

    maximum safety to theoperator, and to control andminimise damage to the rest ofthe switchgear and room.

    11

    Arc absorber reducesoutput impact

    In case it is not possible to ventinto the cable cellar or into anadjacent room, the Xiria designoffers the possibility to safelyvent into the switch room. Inthis case a special arc chimneyis installed at the backside ofthe panel. This arc chimneycontains integrated arcabsorbers that break and filtergasses and fire significantly.

    Controlling an internal arc

    By design, vacuum and air/solidinsulated switchgear has theleast environmental impactafter an internal arc event. Theimpact of an arc is twofold: aninternal impact (in theswitchgear) and external impact(in the switch room).

    The overpressure created by aninternal arc will, in standardswitchgear, be guided out ofthe switchgear by means of apressure relief duct. Next to

    the duct a complicated and

    expensive arc channel may beinstalled, that guides the arcoutput outside the switchroom. The Xiria design isconstructed in such a way thatboth impacts are significantlyreduced and consequently aless complicated arc channel isneeded.

    No phase-to-phase shortcircuits minimises pressure

    Within the Xiria all high voltageparts are single pole insulated.The advantage of this singlepole construction is that theonly conceivable internal fault isa single-phase short circuit, e.g.due to a cable connectionfailure (when single core cablesare connected, as is the normalpractice nowadays).

    11

    An internal arc in switchgear causes an overpressure supported by the release of fire and smoke.

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    12/20

    12

    Capacitive voltage detectionsystem for verification of safe

    isolation from supply

    Each panel type within the Xiriafamily is equipped with astandard three-phase VoltageDetection System for voltagetesting to IEC 61243-5. TheVDS shows the operator if thepanel is isolated from supply ornot.

    Logical mechanical andelectrical interlocks prevent

    mal operation

    Within the Xiria design mis-operation by an operator isprevented by using differentinterlocks. The interlocks aremechanical and electrical. Forexample electrical andmechanical interlocks preventto operate the change-over

    switch when the circuit-breakeris switched on. All mechanical

    interlocks are constructed insuch a way that they directlyblock the mechanism.

    Switching to service positionis only possible with closedcable compartment

    The door of the cablecompartment can only bestandard opened when thecircuit-breaker is in the earthedposition. After the door isremoved it is possible to switchoff the circuit-breaker for cabletesting. Next switching on to

    service position is only possiblewith the door positioned backagain.

    Compartments protectedagainst penetration ofobjects

    Within the Xiria design it is alsonot possible to accidentallypenetrate the switchgear bypart of a body or a tool.

    For the latter all high voltagecompartments have an IP55degree.

    Smooth temporary design

    All compartments of the Xiriapanels are designed in such away that the system is safe totouch from the outside. Byusing a smooth and smartdesign it is not possible for theoperator to injure himself bymoving parts or parts that stickout of the switchgear whenmoving in front of theswitchgear.

    Visible isolation by meansof inspection windows inthe front

    When carrying out operationalactions and work on the cables,it is vital to have unambiguousstatus indications. When itcomes to safety of theoperating personnel Eatonleaves nothing to change. Thatis why the Xiria design is fittedwith directly visible isolation bymeans of inspection windowsin the front which makes theisolating distance between thecable and busbar systemdirectly visible. A visible, short-circuit proof earthing can takeplace via the load-break switchor circuit-breaker.

    Safe in Use

    The Xiria design contains some special features that guarantee the operator to work

    safely with the different panel types.

    What you see is what you get!

    Earth position

    Operating position

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    13/20

    Low Total Cost ofOwnership

    The Xiria design guarantees very low costs related to

    owning the switchgear during its entire lifetime.

    The life-time costs can be split in the initial costs, installation cost,service cost and finally, costs for disposal of the switchgear.

    All costs of owning the switchgear are influenced by differentfeatures of the switchgear. Within Xiria all these features areconstructed in such a way that the costs for the owner are as lowas possible of course with no concessions to the quality of theswitchgear.

    Low initial costsInitial costs consist of purchase,transport, building andinstallation costs.

    Panel width only 500 mm

    By using a combination of solidinsulation technology, electricalfield control and vacuumtechnologies, Eaton's engineersmanaged to construct Xiria Epanels with a width ofmaximum 500 mm. Because atypical switchgear installationnormally consists of a largenumber of panels, this compactdesign significantly reduces theswitch room size. The compactdesign also makes Xiria E highly

    flexible and economicallyattractive when existinginstallations are being replaced.

    Cable connection from thefront (back-to-wallarrangement)

    Cable connection from thefront is a feature that savesbuilding costs. Due to this frontconnection the rear of theXiria E can be installed close tothe wall of a building, againreducing building cost.

    12 kV and 24 kV panels insame housing

    The 12 kV and 24 kV versionsare both accommodated in thesame compact housing. Thismeans substantial savings onbuilding costs because thesame switchroom can be usedwhen the operating voltage isincreased (upgrading).

    Arc chimney with integratedarc absorbers

    A standard option (in case thereis no possibility to vent down

    or backwards) that reduces theswitchroom dimension is theXiria arc chimney withintegrated arc absorbers. Innormal switchgear, gassescaused by an internal arc areguided out of the switchroomby means of an extra duct andarc channel connected to theswitchgear. These additionsrequire extra switch roomspace and consequentlyincreasing initial building cost.

    Low service cost during

    operationService cost consists ofmaintenance, failure andconsequential cost. Besidesthat the technical lifetime ofparts or modules willdetermine the replacementcost of the equipment.

    Robust "lean" design withminimum number of parts

    Costs during service of aswitchgear can be caused bydamaged parts requiring

    replacement, or bymaintenance parts that will notreach their expected lifetime ifthey are not serviced.

    Within the Xiria design aminimal number ofcomponents are used. Thisrobust design with only thenecessary parts is designedbased on experience of buildingswitchgear for more than acentury.

    No SF6-gas pressure checks

    Switchgear that uses SF6-gasas an insulation medium has aleakage rate. To maintain the

    isolation level within this typeof switchgear, the pressure ofthe SF6 tanks must be checkedand refilled on a regular basisduring the unit's lifetime.Within the Xiria, an owner doesnot have to incur the extracosts involved in checking andmaintaining the requiredinsulation level. Thecombination of vacuuminterrupters for switching, solidinsulation and clean air as theinsulation medium, isenvironmentally friendly andmaintains the same quality

    level during the completelifetime of Xiria.

    Primary parts andmechanism installed in afully sealed for live enclosedhousing

    The biggest influence on thequality of the primary andmoving parts in switchgear, hasthe environment in and outsidethe switchroom. Theseenvironmental influences couldin the end cause damage to theswitchgear that should be

    repaired. To prevent anyenvironmental influence onthe most critical parts in theXiria, all of these parts arehoused in a fully sealed for liveenclosure (IP55).

    Product quality guaranteedby prescribed routine testingin the factory

    During production of thepanels, various prescribedroutine tests are carried out byspecialists, making sure thatthe panels achieve the quality

    that they are designed for.

    Low end of life disposal

    cost

    Full recycling or re-use of

    materialsThe primary parts of the Xiriahave a lifetime of at least 30years. Depending on thelocation where the system isinstalled the lifetime can beextended. If for what reasonthe decision is made not to usethe switchgear anymore theXiria can be handed over toEaton again. Next the switch-gear will be dismantled and thedifferent materials can, andwill, be categorised. Becauseno toxic materials are used in

    the Xiria, dismantling is a lesscomplicated, more costeffective and environmentallyfriendly operation. Thedismantled and categorisedmaterials will be, depending onthe material, recycled or re-used.

    13

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    14/20

    User friendly

    First of all requirements is a safe and reliable installation.

    Number two is an installation that is convenient and

    efficient to operate.

    The second aspect does not always get the attention it deserves,but for Xiria most certainly did. The Xiria panels are designed to beuser friendly and are easy to operate.

    Primarily, all operations can be carried out on the front side of thepanel. This means that both cable connection and user interfacefor operation are positioned at the same front side of the panel.The logically arranged control panel enable operators to do theirjob as efficiently and safe as possible.

    Primary cables

    The cable cones of Xiria arepositioned on a height of700 mm from floor level. Thisheight makes it relatively easy

    for operators to connect theprimary cables. There is alsoenough space in the cablecompartment to connect therequired number of cableswith connectors available onthe market.

    Secondary cables

    Connecting the secondarycables is carried out byentering the low voltagecompartment of the Xiria E

    from the top. The low voltagecable terminals are positionedin such a way that the operatorcan connect the cables easilywithin the compartment whilststanding in front of the Xiria E.

    The control panel on the Xiria ispositioned on a convenientheight for the operator. It isdirectly connected to themechanism.

    The mechanism is a handoperated or hand/motoroperated spring chargedmechanism, connected to the

    vacuum interrupters and thechange-over switch. It isoperated via two rotating shaftson the front provided with thenecessary mechanical inter-locks to avoid wrong operation.For example an interlock isbuilt-in that prevents operationof the change-over switchwhen the circuit-breaker orload-break switch is in the ON-position. Another standardfeature on the control panel isthe padlocking of the earthedposition. For padlocking theposition, the most commonpadlocks available in the marketcan be used.

    Manual operation of theswitchgear is achieved withone operating handle. Thishandle can be used forswitching the circuit-breaker,load-break switch and change-over switch. Operation is doneby inserting the handle in theaccess holes in the front. Incase a motor-operated circuit-

    breaker is requested a pushbutton will be installed in thecontrol panel for achieving thisfunction.

    The mechanism is providedwith viewing windows on thefront for direct visual indicationof the earthed position of thechange-over switch and the

    ON/OFF-position of the mainvacuum interrupter. The frontoperating panel is also providedwith a black and white singleline intuitive mimic, showingthe positions of the vacuuminterrupter and the Earth/Busbarposition of the change-overswitch.

    Each panel is provided with avoltage detector mounted onthe front. It is connected viainternal wiring to capacitivesensors inside the cableconnection cones. It shows the

    presence of the primary voltageon all three phases of theprimary cables connected tothe panel.

    In case advanced protectionand control equipment isrequested, the low voltagecompartment positioned on topof the panel, will house these.

    14

    Easy and ergonomic connection of cables

    Clear and simple control panel

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    15/20

    Environmentallyfriendly

    Like all Eaton's other medium voltage switchgear, Xiria

    is designed to be an environmentally friendly product

    throughout the whole chain.

    One of the key strategic initiatives of Eaton is to provide environ-mentally friendly products. Eaton realises that for this they shouldlook at their total product chain, from design to dismantling. Theoptimal situation is that for each phase there is no damage to theenvironment and at the end, all materials can be re-used again inthe same product (the Cradle-to-Cradle principle). The productchain can be divided into four main blocks. These blocks are thedesign (materials used) of the product, the assembly of theproduct, the usage phase of the product and finally thedismantling of the product.

    Eaton's production plant in Hengelo (the Netherlands) acts entirelyin accordance with the rules and procedures of ISO 14001environmental certificate during development and productionprocesses.

    With respect to the design ofswitchgear, the vision "the lessnumber of components thebetter" applies. This becauseevery part must be manu-factured and therefore impactson the environment. Next,applies the affect of differentmaterials on the environment.

    Use of minimised number ofcomponents

    Xiria is designed to use theminimum of materials andresources, without affectingthe strength of the system.For example, Eaton reducedthe number of componentsdramatically, compared toconventional switchgear, byusing an simple spring chargingmechanism and integratedcompartments. This alsoensures straight forward

    assembly with low labour cost.

    Materials with no/lessimpact on the environment

    Eaton selects materials withcare. It is essential that theyare safe for personnel and theenvironment - not just duringuse, but at the end of servicelife too.

    Within Xiria a combination ofsolid (cast resin) insulation andair as insulation medium isused. The solid insulationtechnology, in combination with

    electrical field calculations,provides a very compact,environmentally friendly designfor the switchgear. As the

    switching medium, vacuumtechnology is used within theinterrupters of the Xiria circuit-breakers. Xiria can becompletely recycled at the endof its life without any problem.

    No use of SF6 gas forinsulation or switching

    Within medium voltageswitchgear SF6-gas is beingused, because of its goodinsulating properties. Emissionsof SF6-gas from switchgearcontribute significantly to thethreat of the greenhouse effectand associated climate change.SF6 is on the list of greenhousegasses in the Kyoto protocol.

    SF6 is the most potent of thesix main greenhouse gasses,with a Global WarmingPotential (GWP) of 23,000.

    In the 1980s, the Holec group,as it was then, made afundamental choice not to useSF6 as a switching andinsulation medium for mediumvoltage equipment. In the1980s, Holec had SF6 techno-logy available in-house. Themain reason for not using anySF6 in medium voltage equip-ment was the complexity ofthe treatment required for thetoxicity of the gasses that havebeen in contact with an arc,and the need for additionalsafety measures when used in

    public locations such asresidential areas and shoppingcentres.

    Besides the energy sources,special focus was placed onthe efficient use of materialduring assembly. For example,sheet steel plates are cut withas little waste material aspossible. Residual material isused within other productcomponents.

    15

    Environmentally friendly design Efficient use of materials

    To prevent energy loss by thesystem itself, Xiria uses aminimum number of primarychange-over points. All theavailable change-over pointsuse optimal surface contacts

    and by this, prevent extraenergy losses over thesepoints.

    Minimal energy loss

    during operation

    During dismantling Xiriaswitchgear is demounted intoparts and thereafter categorizedper material. Next the parts willbe recycled or re-used.Because Xiria uses no SF6,

    there is no loss of this gasduring dismantling of theswitchgear.

    Re-use or recycling of

    materials

    Because Xiria is designed fora lifetime of at least 30 years,the system needs no energyusage for maintenanceactivities during this longperiod. Due to the greeninsulation and switchingtechnology, there is also noleakage of the SF6-gas during

    its lifetime and no need forextra maintenance activities onSF6 pressure checks.

    No service checks on site

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    16/20

    16

    Exactly how you want it

    Flexible application of secondary apparatus, protection relays and substation automation

    Eaton realises that end-usershave their own direction withrespect to the use of secondaryapparatus, protection relays andsubstation automation withinthe switchgear. The need forcustomer specific apparatusand relays was taken into

    account during the develop-ment of the Xiria E. Thisresulted in a system thatenables end-users to integrateapparatus according to theirspecification. Thanks to thelarge number of protection andcontrol options, end-users willalways be able to construct anXiria E system that conformsexactly to your requirements.

    Range of Voltagetransformers

    All Xiria E panels can be fittedwith cast-resin insulatedvoltage transformers (of therequested transformer ratio andclass) for the voltagemeasurement on the cable

    side, or on the busbar side.Both transformers can be(dis-)connected safely andeasily.

    Range of Currenttransformers

    The epoxy resin insulatedcurrent transformers are of thering core type. They arepositioned around the primaryconductors behind the cablecones or around the primarycables. All commontransformer ratios, outputs,

    rated currents and classes arepossible.

    Protection and Controlequipment

    The protection and controlequipment is located in the lowvoltage compartment. Thiscompartment is completelyseparate and has its ownaccess door. There is space on

    the door for equipment such asprotection relays, test plugs,meters, etc.

    The Xiria E is standardised forthe Woodward HighProtec linerelays series. However the XiriaE is adaptable for theinstallation of other brands. Incase more than one relay isrequired, the low voltagecompartment can be extended.

    Smart Grids

    Equipment for (remote or local)communication betweenpanels or automation systemscan also be installed in the lowvoltage compartment. Forinstance an Eaton remoteterminal unit (RTU) can be

    applied. Having this possibilitymakes the system the perfectsolution for current and futureSmart Grid applications.

    Simple configuration, coupling and extension

    Every application of this type ofsystem is unique, so Eatonoffers a large number ofdifferent panel types and fieldversions. If, in due course, the

    end-user needs additionalcapacity in the form of morepanels, Xiria E can easily beextended to the right or left.

    Eaton remote terminal unit (RTU).

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    17/20

    Circuit-breaker

    Load-breakswitch

    Change-overswitch

    Motoroperation

    Secondcable

    Capacitivevoltage detection

    system

    Voltagetransformerat the cable

    Currenttransformer

    Option

    Option

    Option

    Option

    Circuit-breaker panel

    M

    Option

    Option

    Option

    Option

    Direct busbar panel*

    Option

    Option

    Option

    Option

    Transformer panel

    M

    Option

    Busbar sectionalizer panel

    M

    Busriser panel*

    Option

    Option

    Option

    Option

    Load-break switch panel

    M

    Option

    M

    Metering panel

    M

    17

    Product Range

    *) Direct busbar and busriser panel available at a later stage.

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    18/20

    18

    Standards

    Xiria E complies with the following international standards

    IEC 62271-1 Common specifications for high-voltage switchgear andcontrol gear standards

    IEC 62271-100 High-voltage alternating-current circuit-breakers

    IEC 62271-102 Alternating current disconnectors and earthing switches

    IEC 62271-103 High-voltage switches

    IEC 62271-200 A.C. metal-enclosed switchgear and control gear for rated voltagesabove 1 kV and up to and including 52 kV

    IEC 62271-304 Additional requirements for enclosed switchgear and control gearfrom 1 kV to 72.5 kV to be used in severe climatic conditions

    IEC 60529 Degrees of protection provided by enclosures

    IEC 60044-1 Instrument transformers - Part 1: Current transformers

    IEC 60044-2 Instrument transformers - Part 2: Inductive voltage transformers

    EN 50181 Plug-in type bushings above 1 kV up to 36 kV

    ISO 9001-2000 Quality

    ISO 14001 Environmental management

    Dimensions (mm)

    Circuit-breaker panel

    Transformer panel

    Load-break switch panel

    Busriser panel

    Busbar sectionaliser panel

    Direct busbar panel

    Metering panel

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    19/20

    Electrical Data

    General 3.6 kV 7.2 kV 12 kV 17.5 kV 24 kV

    Rated voltage kV 3.6 7.2 12 17.5 24

    Impulse withstand voltage kV 40 60 75 / 95 95 125

    Power frequency withstand voltage kV-1m 10 20 28 / 38 / 42 38 50

    Rated frequency Hz 50/60 50/60 50/60 50/60 50/60

    Loss of service continuity LSC2B LSC2B LSC2B LSC2B LSC2B

    Partition class PM PM PM PM PM

    Internal Arc Classification (IAC) AFL AFL AFL AFL AFL

    Internal arc resistance kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1Internal arc resistance with absorber kA - s 16 - 1 16 - 1 16 - 1 16 - 1 16 - 1

    Internal arc resistance cable compartment kA - s 16 - 1 16 - 1 16 - 1 16 - 1 16 - 1

    Internal arc resistance cable comp. alternative kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1

    Degree of protection in service IP31D IP31D IP31D IP31D IP31D

    Degree of protection with doors/covers open IP2X IP2X IP2X IP2X IP2X

    Ambient air temperature range C -25 +40 -25 +40 -25 +40 -25 +40 -25 +40

    Busbar system

    Rated normal current A 630 630 630 630 630

    Rated short-time withstand current kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1

    Rated short time withstand current alternative kA - s 20 - 3 20 - 3 20 - 3 20 - 3 20 - 3

    Rated peak withstand current kA 50 50 50 50 50

    Load break switchesRated normal current A 630 630 630 630 630

    Rated active load break current A 630 630 630 630 630

    Rated short-circuit making current kA 50 50 50 40 40

    Rated short-time withstand current kA - s 20 - 1 20 - 1 20 - 1 20 - 1 20 - 1

    Rated short-time withstand current alternative kA - s 20 - 3 20 - 3 20 - 3 20 - 3 20 - 3

    Rated Cable Charging Breaking Current A 31.5 31.5 31.5 31.5 31.5

    Mechanical Endurance Class M2 5000 x M2 5000 x M2 5000 x M2 5000 x M2 5000 x

    Mechanical Endurance Class as Earth Switch M0 M0 M0 M0 M0

    Mechanical Endurance Class Disconnector M0 M0 M0 M0 M0

    Electrical Endurance Class E3 E3 E3 E3 E3

    Electrical Endurance Class as Earth Switch E2 E2 E2 E2 E2

    Circuit-breakers

    Rated normal current A 630 630 630 630 630Rated breaking current kA 20 20 20 16 16

    Rated short-circuit making current kA 50 50 50 40 40

    Rated Capacitive Switching Current Class C2 C2 C2 C2 C2

    Rated Cable Charging Breaking Current A 31.5 31.5 31.5 31.5 31.5

    DC Time Constant msec 45 45 45 45 45

    DC Component %

  • 8/12/2019 XiriaE_BR_EN_SEA.pdf

    20/20